Inspection
Inspection Details
Equipment ID
15894
15894
Inspection Date
7/15/2025
7/15/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Thomas Jimas
Thomas Jimas
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
24
24
External ID
311356af-bfba-480c-aae3-bd134d749619
311356af-bfba-480c-aae3-bd134d749619
Location
Powell Symphony Hall At Grand Center
718 N Grand Blvd, St. Louis, MO
Phone: (314) 286-4144
718 N Grand Blvd, St. Louis, MO
Phone: (314) 286-4144
Owner
Attn: Cynthia B. Schon
St. Louis Symphony Orchestra
718 N Grand Blvd, St. Louis, MO 63103
Phone: (314) 286-4104
Fax: (314) 544-7004
St. Louis Symphony Orchestra
718 N Grand Blvd, St. Louis, MO 63103
Phone: (314) 286-4104
Fax: (314) 544-7004
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/19/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | Yes | Building removed all attached FAID and Fire Panel. Elevator Red Tagged. | 7/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work, with and without main power, and give proper location. | 7/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Compliant/required documentaion shall be kept in equipment room (neat/orginized) including MCP, etc. | 9/19/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current state operating permit shall be displayed in the equipment room in a non-combustible frame. | 9/19/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work. | 9/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Suspension rope tail ends shall be properly seized/banned. | 9/19/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/19/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Stairs to machine room shall have proper handrail. | 9/19/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | No | No | Machine room shall have GFCI outlet. Currently standard outlet. | 9/19/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Remove old window-style AC unit, fill void with approved fire-resistant materials. | 9/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Remove sheet metal ducting that is hanging from machine room ceiling. | 9/19/2025 |