Inspection
Inspection Details
Equipment ID
3258
3258
Inspection Date
12/18/2018
12/18/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
19
19
External ID
232d7abc-494f-4bb3-a7b7-7d42a6ff3e91
232d7abc-494f-4bb3-a7b7-7d42a6ff3e91
Location
Clark Hall
8001 NATURAL BRIDGE RD, SAINT LOUIS, MO
8001 NATURAL BRIDGE RD, SAINT LOUIS, MO
Owner
UMSL
1 UNIVERSITY BLVD, SAINT LOUIS, MO 63121-4400
1 UNIVERSITY BLVD, SAINT LOUIS, MO 63121-4400
Billing
Attn: UMSL- MSC North Garage
1 UNIVERSITY BLVD, SAINT LOUIS, MO 63121-4400
1 UNIVERSITY BLVD, SAINT LOUIS, MO 63121-4400
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency light in car doesn't work | 12/2/2019 |
| conversion | conversion | n/a | No | No | Door restrictor doesn't work | 12/2/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | All elevators shall have counterweight guards. Guards shall be of unperforated metal of at least the strength of or braced to the equivalent strength of number fourteen (14) gauge sheet steel. Guards shall extend from a point not more than twelve inches (12") above the pit floor to a point not less than seven feet (7') above the pit floor. | 5/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | Phase II Fire Fighters Key Switch operation is intermittently working. The Hold and Off position don't function correctly. | 5/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | All elevators shall have counterweight guards. Guards shall be of unperforated metal of at least the strength of or braced to the equivalent strength of number fourteen (14) gauge sheet steel. Guards shall extend from a point not more than twelve inches (12") above the pit floor to a point not less than seven feet (7') above the pit floor. | 5/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency light does not work when normal power is removed. The alarm bell still works. | 5/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to establish two-way communication | 5/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | All elevators shall have counterweight guards. Guards shall be of unperforated metal of at least the strength of or braced to the equivalent strength of number fourteen (14) gauge sheet steel. Guards shall extend from a point not more than twelve inches (12") above the pit floor to a point not less than seven feet (7') above the pit floor. | 5/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to establish two-way communication | 5/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening. The catch mounted on the door track is worn down. | 5/20/2026 |