Inspection
Inspection Details
Equipment ID
24598
24598
Inspection Date
7/22/2025
7/22/2025
Inspection Type
New Installation
New Installation
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Michael Vantassel
Michael Vantassel
Relief Valve Pressure
NA
NA
Slide
.5
.5
Governor Rope Pull
25/110
25/110
Door Closing Force
20/21
20/21
External ID
ef6311f0-5073-4ac7-bbd6-e7de392856a8
ef6311f0-5073-4ac7-bbd6-e7de392856a8
Location
2647 Locust
2647 Locust, St. Louis, MO
Phone: (314) 443-0949
Email: jimmyp@kaemmerlensolutions.com
2647 Locust, St. Louis, MO
Phone: (314) 443-0949
Email: jimmyp@kaemmerlensolutions.com
Owner
Attn: Mr. Jimmy Powell
Mr. Jimmy Powell
2647 Locust, St. Louis, MO 63104
Phone: (314) 443-0949
Email: jimmyp@kaemmerlensolutions.com
Mr. Jimmy Powell
2647 Locust, St. Louis, MO 63104
Phone: (314) 443-0949
Email: jimmyp@kaemmerlensolutions.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be operational | 12/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 2.26.12 | Yes | No | ost in case of ?re signs on all ?oor openings | 12/10/2025 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 2.26.12 | Yes | No | Correct the position indicator. notes all ?oors as rear door | 12/10/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | Yes | No | Provide an emergency power jewel in the lobby | 12/10/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.16.8 | Yes | No | Test emergency power for ?nal acceptance | 12/10/2025 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | Yes | No | Provide at least a class B rated door for the control space. Control space door shall be self-closing and self-locking | 12/10/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.4.8 Machine Room and Machinery Space | Yes | No | Close all control space penetrations | 12/10/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | Yes | No | Water conveying devices are not allowed in the Control Space | 12/10/2025 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | GFIC receptacle is required in the control space | 12/10/2025 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.5 | Yes | No | Install a heat detector with in 24 in of sprinkler head to activate the shunt trip. | 12/10/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Seal all hoistway penetrations | 12/5/2025 |
| A17.1-2016 : Elevators | 3.11 - Hoistway smoke control | 8.10.2.2.3(q) | Yes | No | Install rated ?re damper in hoistway vent inlet | 12/5/2025 |
| A17.1-2016 : Elevators | 11.3 - Enclosure of Rooms and Spaces | 2.7.1.2 | Yes | No | Machine room backs up to a 2hr rated hoistway and shall also be 2hr rated | 12/5/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Complete ?nal acceptance by testing all heat and smoke detectors | 12/5/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Install a smoke detector in the control space | 12/5/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 | Yes | No | Install the pit light switch adjacent to the pit ladder | 12/5/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Grout the basement door Sill | 12/5/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Raise sprinkler head to hoistway overhead and within 24 inches of the heat detector | 12/5/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Landing shall be near hoistway sill level currently 16inches low | 12/5/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | Yes | No | Test emergency power for final acceptance with jewel properly illuminating. |