Inspection
Inspection Details
Equipment ID
26755
26755
Inspection Date
7/28/2025
7/28/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Chad Hackstadt
Chad Hackstadt
Mechanic Name
Scott Bachman
Scott Bachman
Relief Valve Pressure
440
440
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25F/25R
25F/25R
External ID
867dfc1b-1a48-4ba3-b102-4d8727a907c6
867dfc1b-1a48-4ba3-b102-4d8727a907c6
Location
Ste. Genevieve Middle School
211 N 5th St, Ste. Genevieve, MO
Phone: (000) 000-0000
211 N 5th St, Ste. Genevieve, MO
Phone: (000) 000-0000
Owner
Attn: Michael Horn
Ste. Genevieve R-2 School Dist
375 N 5th St, Ste. Genevieve, MO 63670
Phone: (573) 883-4500 Ext: 2920
Email: mhorn@sgdragons.org
Ste. Genevieve R-2 School Dist
375 N 5th St, Ste. Genevieve, MO 63670
Phone: (573) 883-4500 Ext: 2920
Email: mhorn@sgdragons.org
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 8/16/2024 | |
A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | x | Missing fire extinguisher. | 8/16/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | x | Feeder location needs to be on disconnect. | 8/16/2024 | |
A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Outlets in machine room need to be GFCI. | 8/16/2024 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | The installation of the fire alarm and initiating devices need to be completed and tested. | 8/16/2024 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | Wires in machine room are exposed. | 8/16/2024 | |
A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | x | Machine room needs to be provided with natural or mechanical means to keep ambient air temperature and humidity in the range specified by the elevator equipment manufacturer. | 8/16/2024 | |
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | x | Provide lighting to obtain a minimum of 10 foot candles on all areas of the pit floor. | 8/16/2024 | |
A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Wiring in pit needs to be in conduit. Sump pump wiring running over 6 feet in length shall be enclosed in conduit. | 8/16/2024 | |
A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Remove single non GFI outlet in pit. | 8/16/2024 | |
A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Relocate GFCI in pit to an accessible location. | 8/16/2024 | |
A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | x | Remove screw in ceiling at the top of the hoistway. | 8/16/2024 | |
A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | x | Fire caulk gap in walls, door jams & around beam in hoistway. | 8/16/2024 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | x | NEC - The breaker shall be sized properly for the wire size. | 8/16/2024 | |
A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 3.26.1 | x | NEC 110.26a - Provide code compliant spacing of disconnects in the machine room. | 8/16/2024 | |
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 10/10/2024 | |
A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 3.26.1 | x | NEC 110.26a - Provide code compliant spacing of disconnects in the machine room. | 10/10/2024 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | The installation of the fire alarm and initiating devices need to be completed and tested. | 10/10/2024 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | NEC - The breaker shall be sized properly for the wire size. | 10/10/2024 | |
A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | Relocate GFCI in pit to an accessible location. | 10/10/2024 | |
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 | x | Wires behind ladder need to be in conduit & relocated. 4.5" of clearance from the center line of the ladder rungs to the wall shall be provided. | 10/10/2024 | |
A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | x | Remove screws in ceiling at the top of the hoistway. | 10/10/2024 | |
A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | x | Fire caulk gap in walls, door jams & around beam in hoistway. | 10/10/2024 | |
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | In cab emergency telephone does not work and shall be repaired and tested. | 9/18/2025 |