Inspection
Inspection Details
Equipment ID
203
203
Inspection Date
6/25/2025
6/25/2025
Inspection Type
Alteration
Alteration
Inspector Name
Conde (Cache) Kinsella
Conde (Cache) Kinsella
Mechanic Name
Steven Duffin-Woolfin
Steven Duffin-Woolfin
Relief Valve Pressure
600
600
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
2355031e-0c21-4527-8742-da2885206a6a
2355031e-0c21-4527-8742-da2885206a6a
Location
Marymount Manor
313 Augustine Rd, Eureka, MO
Phone: (636) 938-6770
313 Augustine Rd, Eureka, MO
Phone: (636) 938-6770
Owner
Attn: Mary Mount Manor
Mary Mount Manor
313 Augustine Rd, Eureka, MO 63025
Phone: (636) 938-6770
Email: vspence@rileyspence.com
Mary Mount Manor
313 Augustine Rd, Eureka, MO 63025
Phone: (636) 938-6770
Email: vspence@rileyspence.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Alarm bell is not working. | 10/16/2019 | ||
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Fire service call cancel not working. When call cancel button is pushed, car stops in between floors. | 10/16/2019 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Phone and alarm bell shall work. Ten working days to correct or elevator shall be red-tagged. | 11/23/2020 | |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Fireman's Phase II call cancel, when pushed to cancel call elevator stops, then levels into the next floor. | 11/23/2020 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | Cylinder needs to be repacked. | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit shall be clean and dry. | |||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | Door force too high, should be less than 30 pds. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Use of oil recovery system by automatic means prevents proper monitoring of packing glands and seals. | |||
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Car stopped in the middle of run when car cancel was pushed. Only elevator in building. Red tagged. Repair ASAP. | 9/27/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency alarm not working. | 9/17/2021 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Phone in elevator cab does not work | 9/17/2021 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Alarm bell in elevator cab does not work | 9/17/2021 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Alarm bell in elevator cab not working | 8/4/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace missing / worn cab steadier's | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | Need to provide up-to-date wiring diagrams as part of the MCP | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | x | Post current State Elevator Certificate. | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Car top door operator is missing cover, provide. | |||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Provide existing machine room light to work. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Clean the car top. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Machine room ceiling has water damage, repair or replace as needed. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | Abate black mold on machine room ceiling. | |||
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | OSV is sealed, no tag. Provide testing. Record results. |