Inspection
Inspection Details
Equipment ID
25460
25460
Inspection Date
8/4/2025
8/4/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Travis Cardona
Travis Cardona
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
21
21
External ID
2d56778a-37d9-43eb-a78a-2ffe731360f8
2d56778a-37d9-43eb-a78a-2ffe731360f8
Location
Marriott AC Hotel
215 York Ave, St. Louis, MO
Phone: (000) 000-0000
Email: ac-stlouis@concordhotels.com
215 York Ave, St. Louis, MO
Phone: (000) 000-0000
Email: ac-stlouis@concordhotels.com
Owner
Attn: Carl Hren
One York LLC
11410 Common Oaks Dr, Raleigh, NC 27614
Phone: (314) 887-4846
Email: carl.hren@concordhotels.com
One York LLC
11410 Common Oaks Dr, Raleigh, NC 27614
Phone: (314) 887-4846
Email: carl.hren@concordhotels.com
Billing
Attn: One York LLC
One York LLC
11410 Common Oaks Dr, Raleigh, NC 27614
Phone: (314) 367-2566
Email: ac-stlouis@concordhotels.com
One York LLC
11410 Common Oaks Dr, Raleigh, NC 27614
Phone: (314) 367-2566
Email: ac-stlouis@concordhotels.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4 Instructions for Locating Maintenance Records | x | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/3/2021 | |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.10.2.2.5(b) | x | A counterweight guard shall be installed. | 8/3/2021 | |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.10.2.2.5(b) | x | Counterweight runby signage shall be installed. | 8/3/2021 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | x | Emergency/standby power operation of the elevator shall be tested. | 8/3/2021 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 8/3/2021 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage) | x | Fire service signage shall be installed. | 8/3/2021 | |
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 8.10.2.2.1(d) | x | Permanent flooring shall be installed in the elevator cab. | 8/3/2021 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 10/21/2021 | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/19/2024 | ||
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 2.11 | x | The top and bottom oh horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. The hoistway door safety retainers are missing from the bottom of the door panel and shall be installed. | 7/3/2023 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | The emergency power indicator light at the egress floor must be operational. | 7/3/2023 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 7/3/2023 | |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 2.11 | x | The top and bottom oh horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. The hoistway door safety retainers are missing from the bottom of the door panel and shall be installed. (2nd Notice) | 1/19/2024 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. The emergency power indicator light shall be operational on the egress floor. | 1/19/2024 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | The pit shall be kept clean. Clean the pit. | 1/19/2024 | ||
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The emergency phone is working, but video monitoring is not operational at this time. Take corrective action and re-inspect ASAP. | 1/19/2024 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit needs to be cleaned | |||
| A17.1-2016 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4 | Re-install missing rings on counterweight derailment device and re-inspect counterweight derailment device |