Inspection
Inspection Details
Equipment ID
10006
10006
Inspection Date
8/13/2025
8/13/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Wright
Michael Wright
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
600
600
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
18
18
External ID
f009a092-a43d-4d8a-b4b1-91d244e70559
f009a092-a43d-4d8a-b4b1-91d244e70559
Location
Student Union
500 COLLEGE HL, LIBERTY, MO
Phone: (816) 781-7700
500 COLLEGE HL, LIBERTY, MO
Phone: (816) 781-7700
Owner
Attn: James Hoseth
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 564-1495
Email: hosethj@william.jewell.edu
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 564-1495
Email: hosethj@william.jewell.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | Need to post fire service instuctions in hall by Phase 1 keyswitch. | 4/21/2021 | ||
| conversion | conversion | n/a | Emergency light does not function | 4/21/2021 | ||
| conversion | conversion | n/a | Star braille plate on car operating panel needs to be on G not 1. G is the main fire designated landing. | 4/21/2021 | ||
| conversion | conversion | n/a | elevator phone does not function. | 4/21/2021 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not operate. | 1/21/2019 | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | x | Need to post fire service instructions by phase 1 keyswitch in hall. | 1/21/2019 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | Braille plate for G button in car operating station needs to have a star by it to designate that G is the main fire landing. | 4/21/2021 | ||
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | Post code data plate on controller or mainline disconnect | 4/21/2021 | ||
| A17.1-1996 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 211.9 | Number the controller and power unit for identification. | 4/14/2021 | ||
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Test and log firefighter operation monthly | 4/21/2021 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | Post emergency evacuation of passengers form inside machine room | 4/21/2021 | ||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate inside machine room | 4/21/2021 | ||
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 100.7 | Number inside of hoistway doors for identification | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | Car door restrictors have been disabled | 1/27/2021 | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | All elevators in the same building shall use the same key for firefighter operation | 8/9/2022 | ||
| A17.1-1996 : Elevators | 3.3 - Top-of-car operating device | 210.1d | Top of car inspection station will not run the elevator in the up direction | |||
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Test and log firefighter operation monthly | |||
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 1001.2(c)(15) | Identify the inside of hoistway doors with a numeral corresponding to the landing floor | |||
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 1000.1b(3)(b) Metal Test Tag | Install metal test tag for periodic pressure relief test | |||
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | x | No visual signal during fire recall operation | 8/9/2022 | |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | Car button numerals do not correspond with car postion indicator on car operating panel. | |||
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | x | No visual signal during fire service phase 1 recall. Fire hat on car operating panel and at main landing do not illuminate | 8/8/2023 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency bell does not operate | 8/8/2023 | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | x | Fire hat inside and outside the elevator do not illuminate during fire recall. | 8/13/2025 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1(a)(3) Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency bell does not operate. Batttery needs to be replaced | 8/13/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Car position indicator needs repair so that the position indicator readout corresponds to the floor landing designations. | |||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | State operating certificate not displayed |