Inspection
Inspection Details
Equipment ID
15612
15612
Inspection Date
8/13/2025
8/13/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Wright
Michael Wright
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
360
360
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
21
21
External ID
9ea0e6c9-8cae-424d-9ddb-cfaa69693d53
9ea0e6c9-8cae-424d-9ddb-cfaa69693d53
Location
Melrose Hall
500 College Hl, Liberty, MO
Phone: (816) 365-7641
500 College Hl, Liberty, MO
Phone: (816) 365-7641
Owner
Attn: James Hoseth
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 564-1495
Email: hosethj@william.jewell.edu
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 564-1495
Email: hosethj@william.jewell.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | phone does not operate | 1/15/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not function | 1/21/2019 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency auxillary power does not operate | 1/21/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Post emergency evacuation of passengers procedure inside machine room. | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly. | |
| A17.1-2016 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 | No | No | Cylinder drain line needs to drain into pit container of no more than 5 gallon capacity. | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter operating instructions on car operating panel. | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter operating instructions next to hall fire keyswitch. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate inside machine room. | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Test and log firefighter operation monthly | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Post emergency evacuation of passengers procedure in machine room | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 1000.1b(3)(b) Metal Test Tag | No | No | Install metal test tag for periodic pressure relief test | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No MCP | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance records on site | |
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 100.7 | No | No | Identify inside of hoistway doors with a numeral | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 8/11/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter instructions on car operating panel | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter instructions next to hall firefighter keyswitch | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 10/23/2024 |
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 100.7 | No | No | Identify inside of hoistway door with a numeral | |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Machine room door needs to be self-locking | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed in machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire signage next to hall button fixture at each landing | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Auxiliary lowering unit does not operate | 10/23/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Battery lowering not working. | 8/13/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | "B" jamb tags missing due to vandalism. |