Inspection
Inspection Details
Equipment ID
3356
3356
Inspection Date
8/13/2025
8/13/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Wright
Michael Wright
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
380
380
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
20
20
External ID
6fb59157-3e39-4cf4-a304-8eeb46b6bbf1
6fb59157-3e39-4cf4-a304-8eeb46b6bbf1
Location
Pillsbury Music Building
500 College Hl, Libety, MO
Phone: (816) 781-7700
500 College Hl, Libety, MO
Phone: (816) 781-7700
Owner
Attn: James Hoseth
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 564-1495
Email: hosethj@william.jewell.edu
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 564-1495
Email: hosethj@william.jewell.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly | 8/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Post emergency evacuation of passengers form inside machine room | 8/11/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate inside machine room | 8/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove flammable rags from machine room floor. | 8/11/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove hydraulic oil from pit floor | 8/11/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room | 8/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Remove spare parts for the elevator from the controller. The controller cabinet is not a storage container. | 8/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door lock needs to be self-locking and non-defeatable. | 8/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-locking | 8/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Spare parts can not be stored inside elevator controller. | 8/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No MCP on site | 8/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | No maintenance records on site | 8/11/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed in machine room | 8/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-locking | 8/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove rags from machine floor | 8/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Remove spare parts from the controller cabinet. Controller cabinet is not a storage container | 8/11/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not work | 8/11/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 8/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Provide a self locking door knob for machine room door. | 8/11/2026 |