Inspection
Inspection Details
Equipment ID
7865
7865
Inspection Date
8/15/2025
8/15/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Jason Kempa
Jason Kempa
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
23
23
External ID
da352244-4c17-4235-a1ee-8261ce3efa8a
da352244-4c17-4235-a1ee-8261ce3efa8a
Location
DEA of St. Louis
317 S 16th St, St. Louis, MO
Phone: (314) 538-4600
317 S 16th St, St. Louis, MO
Phone: (314) 538-4600
Owner
Attn: Heather Willis
NGPV St Louis MO LLC
1650 Tysons Blvd, Ste 1500, McLean, VA 22102
Phone: (314) 621-8676 Ext: 26
Email: HW@ngpv.com
NGPV St Louis MO LLC
1650 Tysons Blvd, Ste 1500, McLean, VA 22102
Phone: (314) 621-8676 Ext: 26
Email: HW@ngpv.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.18 - Traction drive machines | 208 | No | No | Machine will not pick up rated capacity due to load weight being out of calibration. | 9/30/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light does not work. | 10/7/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell does not work. | 10/7/2020 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1202.14 | Yes | No | Four (4) suspension ropes are out of their sleeves on the counterweight side. | 10/7/2020 |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 202 | Yes | No | Missing two lock nuts on the bottom of the counterweights. | 10/7/2020 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 1001.2(b)(8) | No | No | Greenfield feeding the bottom slow down limit is broken. Repair so that there are no exposed wires. | 10/31/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide MCP | 9/30/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm inoperable on battery, also emergency light. Re-inspection required | 10/6/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Unable to communicate with emergency personnel over phone. Re-inspection required | 12/15/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Place current state operating certificate in elevator machine room | 7/21/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform the following tests to complete the inspection: full speed counterweight buffer, full load, full speed, car buffer, 125% brake, full load, full speed car safeties, pull out, pull thru, overspeed governor switch and jaw speeds. Re-inspection requireds | 10/30/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator stopped operating during testing, need to perform testing of emergency fire service to complete inspection. Re-inspection required | 8/27/2025 |