Inspection
Inspection Details
Equipment ID
17065
17065
Inspection Date
8/5/2025
8/5/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Roy Gall
Roy Gall
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
8f51e1e8-bed0-46a0-8e67-2f7b02dfe718
8f51e1e8-bed0-46a0-8e67-2f7b02dfe718
Location
Cupples Station Apartments
1023 Spruce St, St. Louis, MO
Phone: (314) 241-1225
Email: pgallagher@fwresults.com
1023 Spruce St, St. Louis, MO
Phone: (314) 241-1225
Email: pgallagher@fwresults.com
Owner
Attn: Cupples Station, LLC
Cupples Station, LLC
1023 Spruce St, St. Louis, MO 63102
Phone: (000) 000-0000
Email: pgallagher@fwresults.com
Cupples Station, LLC
1023 Spruce St, St. Louis, MO 63102
Phone: (000) 000-0000
Email: pgallagher@fwresults.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide MCP | 7/7/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Provide testing | 7/7/2022 |
| A17.1-1996 : Elevators | 4.12 - Standby power selection switch | 1002.2g | No | No | Provide testing | 7/17/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Emergency Power was not transferred to the elevator during testing | 7/7/2022 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | Ropes are rusted and undersized, need to replace all hoist ropes. Re-inspection required | 7/12/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 7/11/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/9/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-WAY COMMUNICATION DEVICE SHALL WORK. No Answer | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually. | |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | No | No | Investigate and repair the source of the grinding noise at the hoist machine. | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. There are no schematics, on-site(as well as fault code lists and parameter tables) | |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 201 | No | No | Need to change worn/damaged upper car roller guides and lower counterweight roller guides. | |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 210.13 | No | No | Replace missing/damaged/faded "Do not use elevator in case of fire" Signage on multiple floors. | |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 210.13 | No | No | Replace damaged Phase 2 instructions inside car. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean. Remove excess debris |