Inspection
Inspection Details
Equipment ID
17356
17356
Inspection Date
8/7/2025
8/7/2025
Inspection Type
Alteration
Alteration
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Thomas Pudelek Jr
Thomas Pudelek Jr
Relief Valve Pressure
480
480
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
6f62af10-0ac2-47b2-989f-2d070fea7264
6f62af10-0ac2-47b2-989f-2d070fea7264
Location
Cardinal Glennon Childrens Hospital
1465 S Grand Blvd, St. Louis, MO
Phone: (314) 268-2771
Alt Phone: (314) 591-1407
Fax: (314) 577-5314
Email: fred.carr1@ssmhealth.com
1465 S Grand Blvd, St. Louis, MO
Phone: (314) 268-2771
Alt Phone: (314) 591-1407
Fax: (314) 577-5314
Email: fred.carr1@ssmhealth.com
Owner
Attn: Madison Himelright
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 577-5307
Email: madison.himelright@ssmhealth.com
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 577-5307
Email: madison.himelright@ssmhealth.com
Billing
Attn: Fred Carr
SSM-Cardinal Glennon Childrens Hospital
1465 S Grand Blvd, St. Louis, MO 63104
Phone: (314) 268-2771
Alt Phone: (314) 591-1407
Fax: (314) 577-5314
Email: fred.carr1@ssmhealth.com
SSM-Cardinal Glennon Childrens Hospital
1465 S Grand Blvd, St. Louis, MO 63104
Phone: (314) 268-2771
Alt Phone: (314) 591-1407
Fax: (314) 577-5314
Email: fred.carr1@ssmhealth.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | The control operating panel is not secured properly to the car enclosure resulting in a substantial gap. The panel shall be properly secured to minimize the exposure to the electrical components. The emergency telephone door is also missing and a new door shall be fabricated. | 6/3/2026 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 7/10/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that either the device is not hooked up to a back-up power device or the back-up power device as failed. Repair for proper operation. Reinspection required. | 7/10/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | 6/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | 6/3/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve (Red Tag) | Yes | Yes | The OSV valve would not stop the car during the Cat 5 full load test. Repair or replace OSV valve and perform full load test. Elevator is Red-tagged and removed from service. Re-inspection required | 6/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | No | No | Remove scavenger line connected to hydraulic jack that returns oil directly to hydraulic tank in elevator machine room. Oil usage should be monitored. Remove scavenger line and place into 5 gallon bucket in elevator pit. | 6/3/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace damaged electrical conduit in hoistway at bottom landing hoistway door, has exposed wiring | 6/3/2026 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 6/3/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that either the device is not hooked up to a back-up power device or the back-up power device as failed. Repair for proper operation. Reinspection required. | 6/3/2026 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Auxiliary lighting inoperable, repair for reinspection. | 6/3/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm signal inoperable, repair for reinspection. | 6/3/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | Yes | No | Provide means to collect and monitor oil loss inside of the elevator pit | 6/3/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | No | Replace damaged electrical conduit in hoistway at bottom landing hoistway door, has exposed wiring | 6/3/2026 |