Inspection
Inspection Details
Equipment ID
16940
16940
Inspection Date
8/6/2025
8/6/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Leland Jones
Leland Jones
Mechanic Name
Jason Hernke
Jason Hernke
Relief Valve Pressure
515
515
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
21
21
External ID
9fc9cf31-9683-4159-9573-c57f26a37c08
9fc9cf31-9683-4159-9573-c57f26a37c08
Location
Ann Hawkins Gentry Middle School
4200 Bethel St, Columbia, MO
Phone: (573) 214-3240
4200 Bethel St, Columbia, MO
Phone: (573) 214-3240
Owner
Attn: Columbia Public Schools
Columbia Public Schools
5909 Paris Rd, Columbia, MO 65202
Phone: (573) 289-1314
Email: trasmith@cpsk12.org
Columbia Public Schools
5909 Paris Rd, Columbia, MO 65202
Phone: (573) 289-1314
Email: trasmith@cpsk12.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Emergency lights are inoperable. | 9/30/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Only one bulb working for normal lighting. Ceiling panels need to be installed. | 9/30/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone must have correct # | 6/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room needs fire extinguisher | 7/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone needs location information for contact | 7/17/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room needs fire extinguisher | 12/21/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Oil on floor needs cleaning | 12/21/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Twin post jacks repacked. Oil and mess needs cleaned up | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | PIT HAS OIL STILL IN THE PIT MUST FIND SOURCE AND CLEAN PIT | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | MUST ADD CLEAR OIL COLLECTION BUCKETS | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | Yes | No | BACK WALL NEEDS BE SECUED TO THE FLOOR | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | Yes | No | MUST REPLACE FLOORING THAT IS MISSING |