Inspection
Inspection Details
Equipment ID
25736
25736
Inspection Date
8/7/2025
8/7/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Travis Cardona
Travis Cardona
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
17F/17R
17F/17R
External ID
47f2a5cf-61ea-467b-98c5-0328f205d019
47f2a5cf-61ea-467b-98c5-0328f205d019
Location
MLS
326 S 21st St, St. Louis, MO
Phone: (314) 511-2294
Email: pcaldwell@stlcitysc.com
326 S 21st St, St. Louis, MO
Phone: (314) 511-2294
Email: pcaldwell@stlcitysc.com
Owner
Attn: Pharron Caldwell
TKFC LC
1 Center Circle, St. Louis, MO 63103
Phone: (314) 339-0401
Email: pcaldwell@stlcitysc.com
TKFC LC
1 Center Circle, St. Louis, MO 63103
Phone: (314) 339-0401
Email: pcaldwell@stlcitysc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. The voice works but video/text does not. | 2/22/2024 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 2.11 | Yes | No | Hoistway door safety retainers/fire tabs shall be installed at the bottom of all hoistway doors. Multiple doors missing retainers. | 2/22/2024 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Emergency lighting shall work. | 2/22/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | Emergency communication loss monitor shall work. | 2/22/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP is present. Needs all the documentation for 2022 & 2023. | 9/12/2024 |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.5 Wedge Rope Sockets | No | No | 2.20.9.5.4 - Hoist rope tail retaining clips shall be properly spaced. | 9/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Adjust upthrust roller bearings for proper clearance to door hanger track (multiple floors). | 9/12/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | 4 x 4 electrical box in machine room needs to have wiring inside box and cover installed. | 9/12/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.19.15 Emergency Communications | Yes | No | Emergency communications loss monitor shall work, activate visual and audible signals indicating the loss of the communication signal. | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | : Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually. | |
| A17.1-2016 : Elevators | 1.20 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.11.2.1.1(y) | No | No | "Earthquake Mode" visual indicator(jewel) in COP shall work, provide cover if not installed, or apply for variance to remove. Unit does not have EQ detection equipment in pit, HW, or MR. No counterweight derailment installed | |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 2.18.6 | Yes | No | Governor - Remote SET/RESET functions shall work as designed. | |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 2.11 | Yes | No | Hoistway door safety retainers/fire tabs shall be installed at the bottom of all hoistway doors. Multiple doors missing retainers. | |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | Counterweight runby does not meet Code Minimum of 6". | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | 4 x 4 electrical box in machine room needs to have wiring inside box and cover installed. | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | MCP - Fire Service must be tested and properly documented monthly on Log Shee | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | MCP, including PM records. No MCP/Records for 2022, 2023, 2024, 2025, 2026 found. |