Inspection
Inspection Details
Equipment ID
3202
3202
Inspection Date
1/14/2019
1/14/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Craig Loveall
Craig Loveall
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
56039d0e-7a9c-49e6-a51d-284c87f6e2a8
56039d0e-7a9c-49e6-a51d-284c87f6e2a8
Location
Drury Inn- St. Joseph
4213 FREDERICK AVE, SAINT JOSEPH, MO
4213 FREDERICK AVE, SAINT JOSEPH, MO
Owner
Attn: General Manager
Drury Inn & Suites
PO BOX 910, CAPE GIRARDEAU, MO 63702
Phone: (000) 000-0000
Drury Inn & Suites
PO BOX 910, CAPE GIRARDEAU, MO 63702
Phone: (000) 000-0000
Billing
Attn: General Manager
Drury Inn & Suites
721 EMERSON RD STE 400, SAINT LOUIS, MO 63141
Phone: (816) 364-4700
Email: Pat.Travers@druryhotels.com
Drury Inn & Suites
721 EMERSON RD STE 400, SAINT LOUIS, MO 63141
Phone: (816) 364-4700
Email: Pat.Travers@druryhotels.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency alarm bell does not function. | 7/30/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Hydraulic oil on machine room floor due to leaking control valve. | 4/4/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit floor has oil accumalation. Oil source is from leak in machine room. | 4/4/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to remove standing hydrauluc oil from elevator pit. Pits need to be kept clean and dry. | 5/6/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post firefighter operating instructions next to hall fire keyswitch | 4/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger pump from pit. Cylinder drain line needs to drain into pit collection container of no more than 5 gallon capacity | 4/29/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | No visual signal during fire recall operation | 4/12/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly | 4/29/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post firefighter operating instructions next to hall fire keyswitch | 4/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire Do Not Use Elevator signage next to lobby corridor call station. | 4/29/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | 110 volt wiring to 3rd and 4th floor stopping switches in the hoistway needs to be in metal conduit | 4/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean elevator car top. | 4/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No maintenance records on site. | 4/29/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | No visual signal during fire recall operation. | 12/16/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger pump from pit. | 4/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove standing water/oil mixture from pit | 4/29/2026 |