Inspection
Inspection Details
Equipment ID
22061
22061
Inspection Date
8/8/2025
8/8/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Chad Hackstadt
Chad Hackstadt
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20F/23R
20F/23R
External ID
4e3befe3-d062-483c-bda9-96446e9e3dc0
4e3befe3-d062-483c-bda9-96446e9e3dc0
Location
Blair School Apts
2707 Rauschenbach Ave, St. Louis, MO
Phone: (314) 899-9762
2707 Rauschenbach Ave, St. Louis, MO
Phone: (314) 899-9762
Owner
Attn: Donichia Sutton
New Blair School LP
261 Gorham Rd, South Portland, ME 04106
Phone: (769) 798-8321
New Blair School LP
261 Gorham Rd, South Portland, ME 04106
Phone: (769) 798-8321
Billing
Attn: Donichia Sutton
Arcway Common Apts
2707 Raushenback Ave, St. Louis, MO 63106
Phone: (314) 899-9762
Email: donichia.sutton@presmgmt.com
Arcway Common Apts
2707 Raushenback Ave, St. Louis, MO 63106
Phone: (314) 899-9762
Email: donichia.sutton@presmgmt.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Phase 1 and Pase 2 fire service did ot operate correctly | 8/20/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 12/11/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | The machine space lighting was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The hoistway door tension on the lower landing shall be repaired to self-close. | 8/4/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The elevator pit shall be cleaned of dust and debris. | 8/26/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Flexible conduit in hoistway needs to be fastened to hoistway ceiling | 5/14/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to clean pit | 5/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | Lighting in hoistway overhead machine space shall work | 5/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 2.18.5 | Yes | No | It appears the governor rope needs to be shortened as the governor tail sheave is at or nearing its full travel. | 8/12/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | Provide code compliant runby. | 8/12/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire Service testing shall be performed and documented monthly. | 9/23/2025 |