Inspection
Inspection Details
Equipment ID
11714
11714
Inspection Date
8/25/2025
8/25/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Michael Beachner
Michael Beachner
Relief Valve Pressure
360
360
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
17
17
External ID
7eeb622c-da2f-456b-a080-fd3670e9aa2a
7eeb622c-da2f-456b-a080-fd3670e9aa2a
Location
Stoney Creek Inn
1201 N Woodbine Rd, St. Joseph, MO
Phone: (816) 901-9600
Email: kerra.flatt@stoneycreekhotels.com
1201 N Woodbine Rd, St. Joseph, MO
Phone: (816) 901-9600
Email: kerra.flatt@stoneycreekhotels.com
Owner
Attn: Kerra Flatt
Stoney Creek Inn
1201 N Woodbine Rd, St. Joseph, MO 64506
Phone: (816) 901-9600
Email: kerra.flatt@stoneycreekhotels.com
Stoney Creek Inn
1201 N Woodbine Rd, St. Joseph, MO 64506
Phone: (816) 901-9600
Email: kerra.flatt@stoneycreekhotels.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.37 - Pressure Switch | 306.14 | x | Need to provide pressure switch on control valve. | 4/11/2019 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not operate. | 6/25/2021 | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Post firefighter operating instructions next to hall fire keyswitch | 11/8/2021 | ||
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | x | x | Momentarily pushing car door open button causes doors to fully open while elevator is on firefighter operation phase 2. 14 days to repair before red tag. | 6/25/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not operate | 1/5/2022 | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Post firefighter instructions next to hall fire service keyswitch | 11/8/2021 | ||
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Test and log firefighter operation monthly | 11/8/2021 | ||
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | x | Car door restrictor does not function | 1/5/2022 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not operate. Phone needs to be reprogrammed | 6/15/2023 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | PHONE DOES NOT RING OUT | 8/16/2024 | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | non elev materials being stored in machroom | 9/23/2025 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | pit floor covered in oil | 9/23/2025 | ||
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | smoke head in mach room not working |