Inspection
Inspection Details
Equipment ID
13722
13722
Inspection Date
8/25/2025
8/25/2025
Inspection Type
Alteration
Alteration
Inspector Name
Michael Amador
Michael Amador
Mechanic Name
Matthew Toettcher
Matthew Toettcher
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
e79a3329-4e4a-45cc-8eac-ffaa3073d3b2
e79a3329-4e4a-45cc-8eac-ffaa3073d3b2
Location
AT & T - One Bell Center
1010 Pine St, St. Louis, MO
Phone: (314) 396-3759
1010 Pine St, St. Louis, MO
Phone: (314) 396-3759
Owner
Attn: c/o Lerch Bates
AT&T Elevator Management
9780 S. Meridian Boulevard, Suite 450, Englewood, CO 80112
Phone: (314) 396-3759
Email: ATT.Elevators@LerchBates.com
AT&T Elevator Management
9780 S. Meridian Boulevard, Suite 450, Englewood, CO 80112
Phone: (314) 396-3759
Email: ATT.Elevators@LerchBates.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Fire service to be tested at later date | 4/22/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Car door restrictor not working | 4/22/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Emergency phone not working | 4/22/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and bell inoperative. Repair | 7/30/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone inoperative. Repair | 7/30/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Restricted opening disabled, inoperative. Repair | 3/18/2024 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Perform fire service operation testing. Phase I and II | 7/30/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Repair inoperative emergency light and alarm bell. | 2/9/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperative emergency phone. | 2/9/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell and emergency light do not work. | 6/2/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor does not function properly. | 6/2/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light is not working. Re-inspection required | 3/18/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2 way communication is not working. Re-inspection required | 3/18/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Door restrictor is disabled. | 7/30/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 3/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Replace CO2 fire extinguisher with ABC. | 3/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Provide missing bottom door guide, hoistway door, 2nd floor. | 3/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Provide existing emergency lights and bell to work. | 7/30/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator on emergency power. | 7/30/2025 |
| A17.1-2016 : Elevators | 4.12 - Standby power selection switch | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator emergency power selector switch. | 7/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. | 3/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting shall work. (Multi-year violation) | 3/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor does not function properly, parts missing. (Multi-year violation) | 3/3/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of the elevator on emergency power and selector switch. (Multi-year violation) | 3/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Provide missing bottom door guide, hoistway door, 2nd floor. (Multi-year violation) | 3/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | Compliant/required documentation & MCP shall be kept in equipment room (neat/organized) including wiring diagrams, and fire service log, recorded monthly. Note: No PM log, callback log, repair log, testing records, or fire service test logs for 2022 - 2025. | 3/3/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. Note: replace CO2 extinguishers in machine room and secondary machine room with ABC type extinguishers. (Multi-year violation) | 5/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | Yes | Car door restrictor does not cuntion properly, parts missing. Multi-year violation. Red tag issued. | 5/15/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of the elevator on emergency power and selector switch. (Multi-year violation) | 5/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Provide missing bottom door guide, hoistway door, 2nd floor. (Multi-year violation) | 5/15/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. (Multi-year violation) | 5/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Compliant/required documentation & MCP shall be kept in equipment room (neat/organized) including wiring diagrams, and fire service log, recorded monthly. Note: No PM log, callback log, repair log, testing records, or fire service test logs for 2022 - 2025. All must be be updated on every vist. | 5/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. Note: replace CO2 extinguishers in machine room and secondary machine room with ABC type extinguishers. (Multi-year violation) | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of the elevator on emergency power and selector switch. (Multi-year violation) | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Provide missing bottom door guide, hoistway door, 2nd floor. (Multi-year violation) | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. (Multi-year violation) | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Compliant/required documentation & MCP shall be kept in equipment room (neat/organized) including wiring diagrams, and fire service log, recorded monthly. Note: No PM log, callback log, repair log, testing records, or fire service test logs for 2022 - 2025. All must be be updated on every vist. |