Inspection
Inspection Details
Equipment ID
10429
10429
Inspection Date
8/19/2025
8/19/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Jason Sutton
Jason Sutton
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
807d3caa-4c21-4ede-af2a-ac744d148006
807d3caa-4c21-4ede-af2a-ac744d148006
Location
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO
Phone: (314) 525-1194
Alt Phone: (314) 313-7488
Fax: (314) 525-1569
Email: jason.delashmit@mercy.net
10010 Kennerly Rd, St. Louis, MO
Phone: (314) 525-1194
Alt Phone: (314) 313-7488
Fax: (314) 525-1569
Email: jason.delashmit@mercy.net
Owner
Attn: Jason DeLashmit
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO 63128
Phone: (314) 525-1194
Alt Phone: (314) 541-5005
Fax: (314) 525-1569
Email: jason.delashmit@mercy.net
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO 63128
Phone: (314) 525-1194
Alt Phone: (314) 541-5005
Fax: (314) 525-1569
Email: jason.delashmit@mercy.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | There is no fireman?s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. | 10/20/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. | 10/20/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | The 3rd floor hoistway door is missing a pick up roller that is required for the car door clutch to work properly. Replace missing pick up roller. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. | 10/20/2020 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | The 3rd floor hoistway door pick up roller that is required for the car door clutch to work properly has deteriorated. Replace pick up roller. | 10/20/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | The car door restrictor device shall be repaired to properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 8/12/2020 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | The elevator pit shall be cleaned of dust and debris. | 10/20/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | Both car door restrictor device’s shall be adjusted so that they will properly catch and restrict the opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 10/29/2020 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | The testing has not been completed on the elevator at this time. The backup emergency power and fireman’s service shall be tested before the inspection is completed. | 8/16/2022 | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | x | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. | 8/4/2025 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency phone must establish two way communication | 8/19/2025 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Generator testing and fire service shall be tested. Scheduled on 8/19/25 | 8/19/2025 | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. | |||
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. | |||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency phone must establish two way communication. Re-inspection required |