Inspection
Inspection Details
Equipment ID
23677
23677
Inspection Date
8/25/2025
8/25/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
15/15
15/15
External ID
07b82137-d402-4627-af2c-ae1a78a317b6
07b82137-d402-4627-af2c-ae1a78a317b6
Location
Vanguard Clayton
8500 Maryland Ave, Clayton, MO
Phone: (314) 410-5213
8500 Maryland Ave, Clayton, MO
Phone: (314) 410-5213
Owner
Attn: Glenn Barnd
Barton Apartments SPE,LLC
8500 Maryland Avenue, St. Louis, MO 63124
Phone: (314) 410-5213
Email: bslmanager@carterhaston.com
Barton Apartments SPE,LLC
8500 Maryland Avenue, St. Louis, MO 63124
Phone: (314) 410-5213
Email: bslmanager@carterhaston.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Seal all penetrations in the hoistway. | 4/27/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | No | Complete installation and testing of components of fire service. | 4/27/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | Repair manual rescue brake release. | 3/19/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Check govenor rope pull through and pull out force. Re-inspection required | 10/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Check governor switch and jaws tripping speed. Re-inspection required | 10/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test drive machine brake with 125% of rated load. Re-inspection required | 10/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test car safeties at rated speed with rated load. Re-inspection required | 10/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test unintended car movement with 125% of rated load. Re-inspection required | 10/19/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean debris from elevator pit. | 10/19/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean dirt from elevator car top | 10/19/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-Communication inoperable and shall be repaired, or replaced. Reinspection required. | 12/20/2024 |