Inspection
Inspection Details
Equipment ID
6395
6395
Inspection Date
12/31/2018
12/31/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
320
320
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
9c143757-3520-482a-854d-86fa219b5c12
9c143757-3520-482a-854d-86fa219b5c12
Location
Prince Hall Family Support Center
4411 N NEWSTEAD AVE, SAINT LOUIS, MO
4411 N NEWSTEAD AVE, SAINT LOUIS, MO
Owner
Prince Hall Family Support Center
4411 N NEWSTEAD AVE, SAINT LOUIS, MO 63115-2534
4411 N NEWSTEAD AVE, SAINT LOUIS, MO 63115-2534
Billing
Attn: OA FMDC-Wainright Bldg
PO BOX 809, JEFFERSON CITY, MO 65102-0809
PO BOX 809, JEFFERSON CITY, MO 65102-0809
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean oil out of the pit. | |||
| MO Minimum : Elevators | (I) - Pits | (I)8 | Put sump pump cover back on. | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No current certificate on display. | |||
| MO Minimum : Elevators | (I) - Pits | (I)5 | Install pit ladder. | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Remove oil from pit. | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit shall be clean and dry. | |||
| MO Minimum : Elevators | (I) - Pits | (I)5 | Install pit ladder. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Seals and glands cannot be monitored for oil loss with automatic pump to put hydraulic fluid back into reservoir. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Remove scavenger unit from pit. | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Expired | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Remove scavenger return line. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Provide means to collect oil in pit. | |||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Phone works but goes to front desk, building empty. Provide another contact with 24/7 monitoring. | ||
| MO Minimum : Elevators | (I) - Pits | (I)5 | Provide permanent means to access the pit. | |||
| MO Minimum : Elevators | (I) - Pits | (I)8 | Replace sump hole cover. | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean pit. | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Sump hole filled with oil, remove. Determine if sump pump works, if not -replace.. |