Inspection
Inspection Details
Equipment ID
11834
11834
Inspection Date
8/19/2025
8/19/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
NA
NA
Slide
14"
14"
Governor Rope Pull
150/550
150/550
Door Closing Force
22
22
External ID
a311d0f1-31ef-42bc-b815-6b971f3c4aac
a311d0f1-31ef-42bc-b815-6b971f3c4aac
Location
Graybar Electric- Clayton
34 N Meramec Ave, Clayton, MO
Phone: (314) 713-3393
34 N Meramec Ave, Clayton, MO
Phone: (314) 713-3393
Owner
Attn: Chase Herbst
Graybar Electric- Clayton
34 N Meramec Ave, Clayton, MO 63105
Phone: (314) 573-6599
Email: chase.herbst@graybar.com
Graybar Electric- Clayton
34 N Meramec Ave, Clayton, MO 63105
Phone: (314) 573-6599
Email: chase.herbst@graybar.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 8/29/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/27/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 9/27/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | A category 5 test shall be performed. | 3/4/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | Fire service in car audible signal shall be operational. | 3/4/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency/standby power operation of the elevator shall be tested. | 3/4/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Yes | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Currently schematics, controller manual, maintenance log, and call-back log are present. | 5/24/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | Emergency power test failed. The elevator shall be able to operate while being powered by the emergency generator. | 5/24/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | The building work in progress includes a remote fire control panel. When work is complete, the tests and requirements of A17.2 item 6.4, A17.1-2005 - 8.10.2.2.6 shall apply. | 5/24/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 11/15/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency power must be tested annually. | 7/24/2024 |