Inspection
Inspection Details
Equipment ID
13826
13826
Inspection Date
3/26/2018
3/26/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Thomas Droege
Thomas Droege
Relief Valve Pressure
Slide
19"
19"
Governor Rope Pull
100/410
100/410
Door Closing Force
25
25
External ID
2e41fc83-96f4-4af7-bcc1-53858527a458
2e41fc83-96f4-4af7-bcc1-53858527a458
Location
Stadium Park East
200 S BROADWAY, SAINT LOUIS, MO
200 S BROADWAY, SAINT LOUIS, MO
Owner
Attn: UNK
Inter Park Holdings, LLC
111 W JACKSON BLVD STE 1900, CHICAGO, IL 60604
Phone: (000) 000-0000
Inter Park Holdings, LLC
111 W JACKSON BLVD STE 1900, CHICAGO, IL 60604
Phone: (000) 000-0000
Billing
Attn: Bill Van Sambeek
Inter Park Holdings, LLC
100 S 9TH ST, SAINT LOUIS, MO 63102
Phone: (000) 000-0000
Email: bill.vansambeek@intpark.com
Inter Park Holdings, LLC
100 S 9TH ST, SAINT LOUIS, MO 63102
Phone: (000) 000-0000
Email: bill.vansambeek@intpark.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 8/25/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell shall work. | 5/28/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Emergency light shall work. | 8/25/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work. | 8/25/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | In car emergency light shall work. | 8/25/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Rope data tag is missing. | 8/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | There is a bad roller guide at the top and bottom of the counterweight. | 8/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace the missing interlock box cover at the orange level. | 8/25/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light shall be guarded. | 8/25/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate in the machine room. | 8/25/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 8/25/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light needs a cover | 8/25/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No up dated Certificates in the Machine Room | 8/25/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(1) Electric elevators Placed out of Service | Yes | Yes | This elevator has been decommissioned and is no longer in service. |