Inspection
Inspection Details
Equipment ID
13837
13837
Inspection Date
3/20/2018
3/20/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Brian Thieme
Brian Thieme
Relief Valve Pressure
Slide
TBD
TBD
Governor Rope Pull
200/425
200/425
Door Closing Force
22
22
External ID
91f46f7f-bcb3-48b8-a537-be9c7416dd16
91f46f7f-bcb3-48b8-a537-be9c7416dd16
Location
Stadium Park West
100 S 9TH ST, SAINT LOUIS, MO
100 S 9TH ST, SAINT LOUIS, MO
Owner
Attn: UNK
Inter Park Holdings, LLC
111 W JACKSON BLVD STE 1900, CHICAGO, IL 60604
Phone: (000) 000-0000
Inter Park Holdings, LLC
111 W JACKSON BLVD STE 1900, CHICAGO, IL 60604
Phone: (000) 000-0000
Billing
Attn: Bill Van Sambeek
Inter Park Holdings, LLC
100 S 9TH ST, SAINT LOUIS, MO 63102
Phone: (000) 000-0000
Email: bill.vansambeek@intpark.com
Inter Park Holdings, LLC
100 S 9TH ST, SAINT LOUIS, MO 63102
Phone: (000) 000-0000
Email: bill.vansambeek@intpark.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Complete category 5 inspection items that still remain (Slide, car & CW buffer, & 125% brake test). | 9/21/2018 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 4/29/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work. | 4/29/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Door closing shall be constant pressure operation on Phase 2 fire service. | 9/21/2018 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Clean the pit. | 4/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | 8.6.4.7.1 - The hoistway shall be kept clean of dirt and rubbish. Clean the hoistway. | 4/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top shall be cleaned. | 4/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | The top and bottom counterweight rollers are worn and require replacement. | 4/29/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator machine room. | 4/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. | 10/23/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Clean the pit. | 10/23/2023 |