Inspection
Inspection Details
Equipment ID
24600
24600
Inspection Date
9/3/2025
9/3/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Tom Worsham
Tom Worsham
Relief Valve Pressure
520
520
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
19
19
External ID
d281d305-848e-4704-b9c9-41f9da92e409
d281d305-848e-4704-b9c9-41f9da92e409
Location
Carpenters Regional Council
1403 Hampton Ave, St. Louis, MO
Phone: (314) 522-1011
Email: dennisn@interfaceconstruction.com
1403 Hampton Ave, St. Louis, MO
Phone: (314) 522-1011
Email: dennisn@interfaceconstruction.com
Owner
Attn: Accounting Department 9th Floor
Mid-America Carpenters Regional Council
12 E Erie St, Chicago, IL 60611
Phone: (312) 787-3076
Mid-America Carpenters Regional Council
12 E Erie St, Chicago, IL 60611
Phone: (312) 787-3076
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency light does not work. Re-inspection required | 10/3/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace missing firefighters Emergency service Phase I signage by keyswitch in lower lobby | 9/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace missing "IN CASE OF FIRE USE STAIRS" signage in lower lobby | 9/30/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 9/30/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | Yes | Emergency phone in car is not working and has no alarm. Red-tagged, Re-inspection required | 10/10/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace missing Firefighters Emergency Service Phase I signage by keyswitch in lower lobby | 9/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace missing "IN CASE OF FIRE USE STAIRS" signage in lower lobby | 9/30/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 9/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace missing Firefighters Emergency Service Phase I signage by keyswitch in lower lobby. | 9/30/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 9/30/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | Yes | Emergency phone in car is not working and has no alarm. Red-tagged, Re-inspection required | 9/30/2025 |