Inspection
Inspection Details
Equipment ID
8594
8594
Inspection Date
8/25/2025
8/25/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Brett Garmon
Brett Garmon
Relief Valve Pressure
660
660
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
17
17
External ID
fba00956-14a5-4f6c-bb9f-4a95d9d89a10
fba00956-14a5-4f6c-bb9f-4a95d9d89a10
Location
Naomi House
3393 McKelvey Rd, Bridgeton, MO
Phone: (314) 591-1660
Email: cwhite@thesarahcommunity.org
3393 McKelvey Rd, Bridgeton, MO
Phone: (314) 591-1660
Email: cwhite@thesarahcommunity.org
Owner
Attn: The Sarah Community
The Sarah Community
12284 De Paul Dr, Bridgeton, MO 63044
Phone: (000) 000-0000
Email: Rodney.smith@thesarahcommunity.org
The Sarah Community
12284 De Paul Dr, Bridgeton, MO 63044
Phone: (000) 000-0000
Email: Rodney.smith@thesarahcommunity.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Need copy of current state operating certificate in machine room. | 10/4/2018 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A completed fire service testing log shall be kept on-site. | 11/6/2020 |
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 211.9 | No | No | Provide car numbering on top of car. | 11/6/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/6/2020 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.1.7 | No | No | 8.6.1.7.5 - The emergency lowering device (ERU) shall be operational. | 11/6/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/18/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 12/8/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 9/18/2025 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | This unit is equipped with an unsealed overspeed valve. Category 5 testing of the overspeed valve shall be completed within 90 days or the elevator will be locked out of service. Overspeed valve originally cited in 2021. There was also no annual inspection in 2022. | 8/22/2024 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. | 9/18/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/18/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering function shall be operational. | 8/22/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. (2nd Notice) | 8/22/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | The auxiliary power lowering operation shall be functional. (2nd Notice) | 9/18/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Emergency power must be tested annually. | 8/4/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/4/2026 |