Inspection
Inspection Details
Equipment ID
14747
14747
Inspection Date
1/4/2019
1/4/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
2
2
Governor Rope Pull
90/470
90/470
Door Closing Force
16
16
External ID
a787e5b5-d3f3-473f-ab17-52dca9a18c57
a787e5b5-d3f3-473f-ab17-52dca9a18c57
Location
Residenses at Forest Park Hotel
4910 W PINE BLVD, SAINT LOUIS, MO
4910 W PINE BLVD, SAINT LOUIS, MO
Owner
Attn: UNK
JES Investments
206 PEACH WAY, COLUMBIA, MO 65203
Phone: (000) 000-0000
Email: dbrown@fairwayconstruction.net
JES Investments
206 PEACH WAY, COLUMBIA, MO 65203
Phone: (000) 000-0000
Email: dbrown@fairwayconstruction.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | emergency alarm and phone back-up battery inoperative repair | 11/11/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm and phone back up battery inoperative. Repair | 10/18/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Maintenance control program shall include written records and procedures for inspections in machine room. | 11/11/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Fire extinguisher in machine room needs to be serviced. | 11/11/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm does not work | 7/25/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm inoperable, does not work on emergency power or regular power. Re-inspection required | 4/1/2025 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Car safeties are stopping the car to fast. Slide shall have a minimum of 2 inches and a maximum of 16 inches. Slide is 1 inch. Car has been red tagged and removed from service until the safeties are adjust and reinspected | 4/4/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell is inoperable | 4/4/2025 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Car safeties are stopping the car to fast. Slide shall have a minimum of 2 inches and a maximum of 16 inches. Slide is 1 inch. Car has been red tagged and removed from service until the safeties are adjust and reinspected | 6/25/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell is inoperable | 6/25/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell is inoperable. Re-inspection required |