Inspection
Inspection Details
Equipment ID
13827
13827
Inspection Date
3/26/2018
3/26/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Thomas Droege
Thomas Droege
Relief Valve Pressure
Slide
23"
23"
Governor Rope Pull
100/390
100/390
Door Closing Force
23
23
External ID
46ce43d1-1bac-4536-a1c1-674bad5e6673
46ce43d1-1bac-4536-a1c1-674bad5e6673
Location
Stadium Park East
200 S BROADWAY, SAINT LOUIS, MO
200 S BROADWAY, SAINT LOUIS, MO
Owner
Attn: UNK
Inter Park Holdings, LLC
111 W JACKSON BLVD STE 1900, CHICAGO, IL 60604
Phone: (000) 000-0000
Inter Park Holdings, LLC
111 W JACKSON BLVD STE 1900, CHICAGO, IL 60604
Phone: (000) 000-0000
Billing
Attn: Bill Van Sambeek
Inter Park Holdings, LLC
100 S 9TH ST, SAINT LOUIS, MO 63102
Phone: (000) 000-0000
Email: bill.vansambeek@intpark.com
Inter Park Holdings, LLC
100 S 9TH ST, SAINT LOUIS, MO 63102
Phone: (000) 000-0000
Email: bill.vansambeek@intpark.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair emergency exit switch. | 8/25/2020 |
| conversion | conversion | n/a | No | No | Replace bad counterweight roller. | 8/25/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work. | 8/25/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 8/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The suspension ropes need to be shortened. | 8/25/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Rope data tag is missing. | 8/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | There is a bad roller guide at the bottom of the counterweight. | 8/25/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate in the elevator machine room. | 8/25/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Clean the pit. | 8/25/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator machine room. | 8/25/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 8/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 8/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency bell shall be operational. | 4/18/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State Operating Certificate is missing in the machine room. | 8/8/2025 |