Inspection
Inspection Details
Equipment ID
18943
18943
Inspection Date
9/10/2025
9/10/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Kevin Hecht
Kevin Hecht
Mechanic Name
Alex Brinkman
Alex Brinkman
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
7ba4561c-a3d3-48d6-94ce-5f45ea1e777a
7ba4561c-a3d3-48d6-94ce-5f45ea1e777a
Location
Wildwood Town Center
16759 Main St, Bldg D, Wildwood, MO
Phone: (314) 727-8889
16759 Main St, Bldg D, Wildwood, MO
Phone: (314) 727-8889
Owner
Attn: Property Manager
BMO-II Wildwood Town Center, LLC
11701 Borman Dr, St. Louis, MO 63146
Phone: (314) 270-5991
Email: ap@intcre.com
BMO-II Wildwood Town Center, LLC
11701 Borman Dr, St. Louis, MO 63146
Phone: (314) 270-5991
Email: ap@intcre.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Need copy of current state operating certificate in machine room. | 1/6/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | Car stop switch is not bypassed on Phase 1 fire recall. | 10/14/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | Yes | No | A monthly fire service testing log shall be kept on-site. | 1/6/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate in the elevator machine room. | 1/6/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | The fire extinguisher is expired and shall be serviced or replaced with a current tested ABC type fire extinguisher. | 8/31/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/31/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 8/31/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/31/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational and code compliant. | 1/26/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/25/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering unit shall work. | 9/25/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/25/2025 |