ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
8.6.1.6.2
|
Yes
|
No
|
Governor sheave will need to be replaced and set safeties on reinspection within 60 days.
|
1/19/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone shall work.
|
7/23/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency communication inoperable. Re-inspection required
|
9/30/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
Yes
|
No
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually.
|
9/22/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
No
|
No
|
Fire service must be tested and documented monthly. No Logs for 2022 - 2025.
|
9/22/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP, repair/PM/Callback logs for 2022 - 2025.
|
9/22/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
9/22/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
No
|
No
|
Fire service must be tested and documented monthly. No Logs for 2022 - 2025.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP, repair/PM/Callback logs for 2022 - 2025.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|