Inspection
Inspection Details
Equipment ID
6834
6834
Inspection Date
9/19/2025
9/19/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas Krug
Thomas Krug
Mechanic Name
Donald Miles
Donald Miles
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
23
23
External ID
53222bac-b755-4779-b449-f3b12b5920bf
53222bac-b755-4779-b449-f3b12b5920bf
Location
The Ritz-Carlton
100 Carondelet Plz, St. Louis, MO
Phone: (314) 719-1445
100 Carondelet Plz, St. Louis, MO
Phone: (314) 719-1445
Owner
Attn: Ritz Carlton Hotel
Ritz Carlton Hotel
100 Carondelet Plz, St. Louis, MO 63105
Phone: (314) 863-6300
Email: rebecca.schwab@marriott.com
Ritz Carlton Hotel
100 Carondelet Plz, St. Louis, MO 63105
Phone: (314) 863-6300
Email: rebecca.schwab@marriott.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove oil from pit floor | 9/22/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Accumulated oil in pit | 9/22/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | Emergency communication failure detection system shall work. | 3/21/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power to be tested with rated load. | 3/21/2025 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | Machine room outlests to be GFI protected. | 3/21/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | Machine room 4x4 box shall have wiring inside box and cover installed. | 3/21/2025 |
| A17.1-2016 : Elevators | 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches | 2.29.1 | Yes | No | Machine room machinery, controllers, governors, disconnects, etc. shall have proper numbering. | 3/21/2025 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | Yes | No | Controller code data plate is blank. | 3/21/2025 |
| A17.1-2016 : Elevators | 5.6 - Governor-rope tension devices | 2.18.7 | Yes | No | Shorten governor rope to allow proper pit clearance of tail-sheave. Currently only about 1/2" clearance to pit floor. | 3/21/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | All applicable FAID will be tested with all 5 tractions cars online. | 3/21/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | 8.6.4.12.1 While compressing the car buffer, the elevator strikes the governor tail sheave causing the safeties to engage before the buffer is fully compressed. 2.4.1.5 When the car is resting on its fully compressed buffers or bumpers, no part of the car, or any equipment attached thereto or equipment traveling with the car, shall strike any part of the pit or any equipment mounted therein. |