Inspection
Inspection Details
Equipment ID
23903
23903
Inspection Date
9/18/2025
9/18/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Christopher McCarty
Christopher McCarty
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
Front 24. Rear 28
Front 24. Rear 28
External ID
da15c513-b69e-4020-8b63-4a2b3a9d3edc
da15c513-b69e-4020-8b63-4a2b3a9d3edc
Location
Fairfield Inn/ Residence
11920 Westline Industrial Dr, St. Louis, MO
Phone: (000) 000-0000
11920 Westline Industrial Dr, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Fairfield Inn
Midas Westport II, LLC
1804 Borman Circle Dr, Ste 100, St. Louis, MO 63146
Phone: (314) 764-4262
Email: kprainito@midashospitality.com
Midas Westport II, LLC
1804 Borman Circle Dr, Ste 100, St. Louis, MO 63146
Phone: (314) 764-4262
Email: kprainito@midashospitality.com
Billing
Attn: c/o ATIS - Certificate Management
Midas Hospitality
600 Emerson Rd, Suite 225, St. Louis, MO 63141
Phone: (314) 441-3983
Email: MidasHospitality@atis.com
Midas Hospitality
600 Emerson Rd, Suite 225, St. Louis, MO 63141
Phone: (314) 441-3983
Email: MidasHospitality@atis.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 2/19/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Remove Water from pit | 11/1/2019 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Need maintenance control program on site posted on controller on or by next test | 12/21/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Need testing procedures in the MCP on or before 1/1/22 | 12/20/2021 |
| A17.1-2016 : Elevators | 5.6 - Governor-rope tension devices | 8.11.2.1.5(g) | No | No | Replace rusting conduit to Governor tail sheave switch 620.21 | 1/3/2023 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.2.1.5(a) | No | No | Channel pit floor to sump pump to drain standing water. 2.2.2.3 | 1/3/2023 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(f) | No | No | Repair machine space lighting top of hoistway 2.7.6.3.2(c) | 1/3/2023 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.3.2 (Re-Inspection) | Yes | No | Hoisting belts have rouge all over need to be replaced | 10/19/2023 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.19.3 | Yes | No | Replace rusting pipe to govenor weight tail switch | 10/19/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Yes | No | Replace rusting piping to governor weight tasil switch has not been corrected | 11/3/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Reinspection for rusted piping for tail shiv in pit, not corrected. Will have until Jan 15, 2024 to complete | 1/15/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Yes | No | Repair switch push buttons in phase 2 fire service panel in car | 2/26/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | REMOVE WATER FORM THE PIT FLOOR | 11/6/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | POST CURRENT STATE CERTIFICATE IN THE MACHINE SPACE | 11/6/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | Yes | Yes | Repair Switches in Phase 2 Fire Service Panel ( Call Cancel - Door open - Door Close ) Item 6.4 Section 2.27.3 | 2/19/2026 |