Inspection
Inspection Details
Equipment ID
7561
7561
Inspection Date
9/19/2025
9/19/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Scott Fischer
Scott Fischer
Relief Valve Pressure
590
590
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
28
28
External ID
b4f58063-7c64-4f4e-8d86-cf28b9ab8ab6
b4f58063-7c64-4f4e-8d86-cf28b9ab8ab6
Location
3251 Riverport
3251 Riverport Ln, Maryland Heights, MO
Phone: (314) 447-8007
3251 Riverport Ln, Maryland Heights, MO
Phone: (314) 447-8007
Owner
Attn: Tiara Nash
Riverport Holding, LLC
200 N Broadway, Ste 130, St. Louis, VA 63102
Phone: (314) 241-0082
Email: Tiara.Nash@cushwake.com
Riverport Holding, LLC
200 N Broadway, Ste 130, St. Louis, VA 63102
Phone: (314) 241-0082
Email: Tiara.Nash@cushwake.com
Billing
Attn: Ellen Gentry
Riverport Holding, LLC
200 N Broadway, Ste 130, St. Louis, MO 63102
Phone: (314) 241-0082
Email: Ellen.Gentry@cushwake.com
Riverport Holding, LLC
200 N Broadway, Ste 130, St. Louis, MO 63102
Phone: (314) 241-0082
Email: Ellen.Gentry@cushwake.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | No | No | Scavenger pumps that do not record the amount of oil returned to the hydraulic tank cannot be installed in the elevator pit. Either install a recordable scavenger pump or limit the amount of oil stored in the pit to 5 gallons. | 3/22/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written maintenance control program shall be kept on site for each elevator. | 3/22/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired | 8/19/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Auxiliary power unit not working, repair and retest | 10/25/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Car failed 15 minute stand test,repair and retest | 10/25/2021 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Unsealed | 8/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger line. | 8/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Provide pit bucket | 8/19/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | No | No | Remove scavenger unit from pit. | 3/22/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide MCP. | 3/22/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired | 3/22/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Auxiliary power unit not working. | 8/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger line. | 3/22/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current certificate. | 3/25/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Unit failed 15 minute stand test. Repair and retest. | 10/31/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery backup lowering unit not working correctly. | 10/31/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Emergency battery lowering device shall work. Re-inspection required | 11/25/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | Lighting in machine room shall not be controlled by automatic means only. Replace timed light switch with on/off switch. | 12/3/2024 |