Inspection
Inspection Details
Equipment ID
12091
12091
Inspection Date
9/25/2025
9/25/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Ronnie Morris
Ronnie Morris
Relief Valve Pressure
Na
Na
Slide
Incomplete
Incomplete
Governor Rope Pull
Incomplete
Incomplete
Door Closing Force
Incomplete
Incomplete
External ID
f2b89daf-04b8-4587-ad2a-cd151228dfc5
f2b89daf-04b8-4587-ad2a-cd151228dfc5
Location
Renaissance Grand Hotel- St. Louis
800 Washington Ave, St. Louis, MO
Phone: (314) 621-9600
800 Washington Ave, St. Louis, MO
Phone: (314) 621-9600
Owner
Attn: Marriott St. Louis Grand
Marriott St. Louis Grand
800 Washington Ave, St. Louis, MO 63101
Phone: (314) 333-2326
Alt Phone: (314) 418-5858
Email: Katherine.Hannibal@marriott.com
Marriott St. Louis Grand
800 Washington Ave, St. Louis, MO 63101
Phone: (314) 333-2326
Alt Phone: (314) 418-5858
Email: Katherine.Hannibal@marriott.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.1 - Top-of-car stop switch | 210.2(h) | No | No | Car top switch on door operator is broken. Repair | 9/30/2025 |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 202 | Yes | No | Counterweight siesmic displacement detection does not open door. | 1/14/2020 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | Suspension ropes are crossed and are impinging on rope pocket/machine room floor. | 1/14/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone does not connect to 24x7 security. | 3/28/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the elevator machine room | 9/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair cab steadier on top of car, cab is not sturdy | 9/30/2025 |
| A17.1-1996 : Elevators | 3.1 - Top-of-car stop switch | 210.2(h) | No | No | Car top switch on door operator is broken. Repair (could not confirm) | 10/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Repair cab steadier on top of car, cab is not sturdy. (could not confirm) | 10/16/2025 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | Yes | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. This currently is an unsafe condition as temporary means of keeping the machine room space cool has resulted in the equipment being open to the elements. Reinspection is required. | 10/16/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 10/16/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | This unit has not had a documented annual inspection performed since 3/28/22 and the last category 5 test was 3/5/2018. This elevator shall have a full category 5 test completed within 15 days. Failure to comply in this time frame will result in the elevator placed out of service with a red tag issued. Only a machine room inspection has been performed at this time. | 10/16/2025 |
| A17.1-1996 : Elevators | 3.1 - Top-of-car stop switch | 210.2(h) | No | No | Car top switch on door operator is broken. Repair (could not confirm) | 11/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Repair cab steadier on top of car, cab is not sturdy. (could not confirm) | 11/5/2025 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | Yes | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. This currently is an unsafe condition as temporary means of keeping the machine room space cool has resulted in the equipment being open to the elements. Reinspection is required. | 11/5/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Note: This is part of a Category 5 and Category 1 test. | 11/5/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | This unit has not had a documented annual inspection performed since 3/28/22 and the last category 5 test was 3/5/2018. This elevator shall have a full category 5 test completed before the elevator can be returned to service. | 11/5/2025 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. This currently is an unsafe condition as temporary means of keeping the machine room space cool has resulted in the equipment being open to the elements. Reinspection is required. | 6/1/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Repair or replace car door operators both rear and front. | 6/1/2026 |
| A17.1-1996 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10.1.2 - Protection not functioning | Yes | No | Seismic operations failed. Repair or replace. | 6/1/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Testing of emergency generator standby power needs to be scheduled, tested and witnessed by an inspector to complete inspection. Re-inspection required | |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | Provide front car door restrictor to work. Re-inspection required | |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | Yes | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. This currently is an unsafe condition as temporary means of keeping the machine room space cool has resulted in the equipment being open to the elements. Reinspection is required. |