Inspection
Inspection Details
Equipment ID
5805
5805
Inspection Date
9/10/2025
9/10/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Michael Vantassel
Michael Vantassel
Relief Valve Pressure
TBD
TBD
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
d2d07527-a42c-4975-b243-671c098e6850
d2d07527-a42c-4975-b243-671c098e6850
Location
Hampton Inn- Maryland Heights
2454 Old Dorsett Rd, Maryland Heights, MO
Phone: (314) 298-7878
2454 Old Dorsett Rd, Maryland Heights, MO
Phone: (314) 298-7878
Owner
Attn: Double Star Maryland Heights LLC
Double Star Maryland Heights LLC
113 Eston Way, Mount Juliet, TN 37122
Phone: (000) 000-0000
Email: christa.day@hilton.com
Double Star Maryland Heights LLC
113 Eston Way, Mount Juliet, TN 37122
Phone: (000) 000-0000
Email: christa.day@hilton.com
Billing
Attn: Hampton Inn- Maryland Heights
Hampton Inn- Maryland Heights
2454 Old Dorsett Rd, Maryland Heights, MO 63043
Phone: (000) 000-0000
Email: christa.day@hilton.com
Hampton Inn- Maryland Heights
2454 Old Dorsett Rd, Maryland Heights, MO 63043
Phone: (000) 000-0000
Email: christa.day@hilton.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (F) - Electrical Switches | (F)3 | Yes | No | Need to replace alarm button. 1.3 | 10/14/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | No | No | Door restrictor needs to work. 1.18 Reinspection Required. | 10/14/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Fire service Phase I key switch is labeled wrong. Repair and reinspect within 30 days. | 6/9/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Control valve pressure relief setting is not sealed. Perform required testing and seal within 30 days, on or before 9/11/20 | 5/19/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit lighting is not working. | 9/26/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | The hall fire hat jewel must illuminate when on fire service operation. | 12/18/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | 12/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational on auxiliary power. | 12/18/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | 12/18/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water and oil shall not be allowed to accumulate on pit floors. There is oil on the pit floor possibly from a leaky fitting. | 12/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | There is a hole in the car operating panel due to a missing key-switch. The key-switch shall be replaced or the hole shall be covered. | 12/18/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The relive valve setting shall be tested. The test is incomplete due to ID 5804 being red-tagged. | 12/18/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | The hall fire hat jewel must illuminate when on fire service operation. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water and oil shall not be allowed to accumulate on pit floors. There is oil on the pit floor possibly from a leaky fitting. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | There is a hole in the car operating panel due to a missing key-switch. The key-switch shall be replaced or the hole shall be covered. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The relive valve setting shall be tested. The test is incomplete due to ID 5804 being red-tagged. |