Inspection
Inspection Details
Equipment ID
13721
13721
Inspection Date
9/8/2025
9/8/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
NA
NA
Slide
43"
43"
Governor Rope Pull
600
600
Door Closing Force
14
14
External ID
de198d13-b10c-4e30-894e-19a5507d8ddd
de198d13-b10c-4e30-894e-19a5507d8ddd
Location
AT & T - One Bell Center
1010 Pine St, St. Louis, MO
Phone: (314) 396-3759
1010 Pine St, St. Louis, MO
Phone: (314) 396-3759
Owner
Attn: c/o Lerch Bates
AT&T Elevator Management
9780 S. Meridian Boulevard, Suite 450, Englewood, CO 80112
Phone: (314) 396-3759
Email: ATT.Elevators@LerchBates.com
AT&T Elevator Management
9780 S. Meridian Boulevard, Suite 450, Englewood, CO 80112
Phone: (314) 396-3759
Email: ATT.Elevators@LerchBates.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Fire service to be tested at a later date. | 3/22/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light inoperative, repair. | 3/28/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Perform fire service operation testing. Phase I and II | 3/28/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Repair inoperative emergency light. | 2/9/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Repair inoperative emergency phone. | 2/9/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and alarm bell do not work. | 6/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting is not working. Re-inspection required | 11/18/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2 way communication is not working. Re-inspection required | 11/18/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | Yes | 2-way communication is not working. Elevator red tagged as this violation first cited in 2022 and is still not corrected. | 12/3/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Governor safety rope pull out exceeds 30" maximum allowable (68" actual pull out). Elevator Red Tagged. | 12/3/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | Yes | Emergency lighting is not working. Elevator red tagged as this violation first cited in 2022 and is still not corrected. | 12/3/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 12/3/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete; Items still needed: all weight tests, buffer tests, governor speeds, governor pullout/pull-thru, slide, fire service, door pressure, EP. Must be completed within 60 days. | 12/3/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 9/29/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current ABC type fire extinguisher shall be provided in the secondary machine room. | 9/29/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting needs to be repaired. One or more bulbs are not working. | 9/29/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting is not working. | 9/29/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 9/29/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete; Items still needed: all weight tests, buffer tests, governor speeds, governor pullout/pull-thru, slide, fire service, door pressure, EP. | 9/29/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 3/3/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | Machinery, controllers, governors, disconnects shall be numbered. All governors need to be numbered. | 3/3/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Remove excess debris. | 3/3/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | Emergency exit shall be properly secured. | 3/3/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. No PM/callback/repair logs, or testing records for 2022-2025. | 3/3/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service shall be tested and documented monthly. No log for 2022-2025. | 3/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Replaced CO2 fire extinguisher in machine room and secondary spaces with ABC type. Multi-year violation. | 3/3/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting needs to be repaired. One or more bulbs are not working. | 3/3/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | Overspeed governors in secondary shall be numbered to their corresponding machines. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Compliant/required documentation shall be provided in the machine room. PM log, callback log, repair log, testing records, and monthly fire service testing log. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State operating certificate shall be displayed in the machine room in a non-combustible frame. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | Car top emergency exit shall be properly secured. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing or elevator on emergency power selector switch. Was not tested in 2025. |