Inspection
Inspection Details
Equipment ID
8780
8780
Inspection Date
9/25/2025
9/25/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Tommy Hogge
Tommy Hogge
Mechanic Name
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
0f7bf0fa-d09c-48df-bf49-b7200c98077f
0f7bf0fa-d09c-48df-bf49-b7200c98077f
Location
200 South Hanley Bldg
200 S Hanley Rd, Clayton, MO
Phone: (314) 721-7360
200 S Hanley Rd, Clayton, MO
Phone: (314) 721-7360
Owner
Attn: Owner / Operator
Scott Properties- Hanley
1065 Executive Parkway Dr, St. Louis, MO 63141
Phone: (000) 000-0000
Scott Properties- Hanley
1065 Executive Parkway Dr, St. Louis, MO 63141
Phone: (000) 000-0000
Billing
Attn: Carol Crawford
Scott Properties c/o CBRE
1807 Park 270 Dr, Ste 465, St. Louis, MO 63146
Phone: (314) 899-5030
Scott Properties c/o CBRE
1807 Park 270 Dr, Ste 465, St. Louis, MO 63146
Phone: (314) 899-5030
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The hoist ropes need to be shortened. | 9/3/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 4/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 6/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The person answering the emergency phone shall be able to identify the location of the elevator. | 6/15/2022 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)11 | No | No | Wedge rope socket is anchored incorrectly. When the steel wire rope has been seated in the wedge socket by the load on the rope, the wedge shall be visible, and at least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope. The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. | 1/2/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 1/2/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/2/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | The counter-weight guard shall extend from a point not more than twelve inches above the pit floor to a point not less than seven feet above the pit floor. | 1/2/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Only such electrical wiring, raceways, cables, coaxial wiring, and antennas used directly in connection with the elevator shall be permitted to be installed inside the machine room. Remove coaxial wiring. | 1/2/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two way communication phone does not work. Repair or replace code 2.27.1 | 10/1/2025 |