Inspection
Inspection Details
Equipment ID
8650
8650
Inspection Date
9/24/2025
9/24/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
23
23
External ID
dbb6d65f-ca1e-4965-b5e6-6b2b2fc12268
dbb6d65f-ca1e-4965-b5e6-6b2b2fc12268
Location
Clayton Corporate Park Management Company
600 Corporate Park Dr, Clayton, MO
Phone: (314) 512-2602
Email: William.j.langenstein@ehi.com
600 Corporate Park Dr, Clayton, MO
Phone: (314) 512-2602
Email: William.j.langenstein@ehi.com
Owner
Attn: Joe Langenstein
Clayton Corp Park Management Company
700 Corporate Park Dr, Clayton, MO 63105
Phone: (314) 512-2602
Email: William.j.langenstein@ehi.com
Clayton Corp Park Management Company
700 Corporate Park Dr, Clayton, MO 63105
Phone: (314) 512-2602
Email: William.j.langenstein@ehi.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace hoist cables due to diameter reduction. | 9/16/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Written maintenance control program shall be kept on site for each elevator. | 12/18/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1993), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 10/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | 9/10/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The smoke detector at the top of the hoistway has become detached and shall be resecured in the electrical junction box. | 10/1/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 9/10/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Governor rope is rouged and undersized. Need to replace the governor rope. Re-inspection required | 10/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1993), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 10/1/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA phone is not working. Re-inspection required | 10/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The smoke detector at the top pf the hoistway has become detached and shall be secured to the electrical junction box. | 10/1/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Re-inspection required | 10/1/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA phone is not working. Re-inspection required | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | The smoke detector at the top of the hoistway has become detached and shall be resecured in the electrical junction box. | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Governor rope is rouged and undersized. Need to replace the governor rope. Re-inspection required |