Inspection
Inspection Details
Equipment ID
12482
12482
Inspection Date
9/19/2025
9/19/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Tommy Hogge
Tommy Hogge
Mechanic Name
Michael Vantassel
Michael Vantassel
Relief Valve Pressure
280
280
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
17
17
External ID
3dd5d1fe-8097-416e-876b-a9ae5fee6c5b
3dd5d1fe-8097-416e-876b-a9ae5fee6c5b
Location
Villa Dorado Condo
11845 Cresta Verde Dr, St. Louis, MO
Phone: (636) 733-9021
11845 Cresta Verde Dr, St. Louis, MO
Phone: (636) 733-9021
Owner
Attn: Ashford Condominium Association c/o Civitas Real Estate Services
Ashford Condominium Association c/o Civitas Real Estate Services
7292 Manchester Rd., Maplewood, MO 63143
Phone: (314) 371-0035
Ashford Condominium Association c/o Civitas Real Estate Services
7292 Manchester Rd., Maplewood, MO 63143
Phone: (314) 371-0035
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | Machine room door has no self-closing, self-locking feature. | 10/2/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Pit light inoperative. | 10/2/2025 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room door must be self closing and lockable. | 10/2/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 9/2/2022 | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Pit light shall work | 10/2/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher in machine room is expired, replace or have serviced | 10/2/2025 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency phone in car unable to provide location, needs to be upgraded to do so. Re-inspection required | 8/17/2023 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | 10/2/2025 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | x | Provide machine room door to be self closing and self locking. | 10/2/2025 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Phone works, but unable to communicate (bad number). Reprogram phone. | 10/2/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher in machine room is expired, replace or have serviced | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | |||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Phone works, but unable to communicate (bad number). Reprogram phone. Re-inspection required |