Inspection
Inspection Details
Equipment ID
8778
8778
Inspection Date
10/1/2025
10/1/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
600
600
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
26
26
External ID
43e4b3c5-b828-43ce-85bc-304a3bf9dcb8
43e4b3c5-b828-43ce-85bc-304a3bf9dcb8
Location
Shrewsbury Community Center
5200 Shrewsbury Ave, St. Louis, MO
Phone: (314) 647-1003
Email: cbuck@cityofshrewsbury.com
5200 Shrewsbury Ave, St. Louis, MO
Phone: (314) 647-1003
Email: cbuck@cityofshrewsbury.com
Owner
Attn: Chris Buck
Shrewsbury Community Center
5200 Shrewsbury Ave, St. Louis, MO 63119
Phone: (314) 647-1003
Email: cbuck@cityofshrewsbury.com
Shrewsbury Community Center
5200 Shrewsbury Ave, St. Louis, MO 63119
Phone: (314) 647-1003
Email: cbuck@cityofshrewsbury.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency lights shall work | 9/4/2018 |
| conversion | conversion | n/a | No | No | Seal rupture valve | 9/4/2018 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emergency light not working. | 9/4/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell not working. | 11/27/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperative emergency phone. | 9/9/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone rings to police. Reprogram phone and reinspect. | 9/29/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell does not work. | 9/29/2021 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Bottom floor hoistway door pick-up roller assembly has one roller, requires two. | 9/22/2022 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(4) | No | No | Cylinder packing is worn and leaking. | 9/22/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 9/22/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Valve not sealed | 9/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP | 9/22/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired | 9/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The position indicating or “PI” device in the car was not operational on the day of inspection. Repair “PI” device to indicate the position of the elevator car. | 12/5/2023 |