Inspection
Inspection Details
Equipment ID
23267
23267
Inspection Date
10/3/2025
10/3/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Chad Hackstadt
Chad Hackstadt
Mechanic Name
Donald Miles
Donald Miles
Relief Valve Pressure
650
650
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
efbc8e45-6a4b-437e-827c-5f90389e7cc3
efbc8e45-6a4b-437e-827c-5f90389e7cc3
Location
The Boulevard
3330 Ehlmann Rd, St. Charles, MO
Phone: (000) 000-0000
3330 Ehlmann Rd, St. Charles, MO
Phone: (000) 000-0000
Owner
Attn: Kelly Arnold
Boulevard Senior Living St. Charles
3330 Ehlmann Rd, Boca Raton, FL 33486
Phone: (417) 893-6006
Email: karnold@boulevardseniorliving.com
Boulevard Senior Living St. Charles
3330 Ehlmann Rd, Boca Raton, FL 33486
Phone: (417) 893-6006
Email: karnold@boulevardseniorliving.com
Billing
Attn: Kelly Arnold
The Boulevard
3330 Ehlmann Rd, St. Charles, MO 63301
Phone: (314) 258-3441
Alt Phone: (636) 757-5077
Email: karnold@boulevardseniorliving.com
The Boulevard
3330 Ehlmann Rd, St. Charles, MO 63301
Phone: (314) 258-3441
Alt Phone: (636) 757-5077
Email: karnold@boulevardseniorliving.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lighting shall be operational. | 7/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including onsite documents. | 1/18/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/27/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 9/27/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. Based on the installation year, the unit is overdue for a category 5 test. The overspeed valve shall be tested with the rated load on or before the next annual inspection. | 10/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational. | 2/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The emergency power indicator light in the main elevator lobby shall illuminate when the car is running on the emergency standby power. | 2/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of the findings for firefighters service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation and the date shall be available on site. | 2/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.16 - Rated load, platform area, and data plate | 2.16.3.1 Capacity Plates | No | No | The in car capacity plate shall indicate the rated load of the elevator. The current capacity tag is incorrect. The rated load of this elevator is 3500 lbs. | 2/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | Each elevator in the building shall be assigned a unique alphabetical or numerical identification adjacent to or on every elevator entrance at the designated level. | 2/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | Yes | No | The overspeed valve is not properly sealed. It shall be tested with the rated load within 90 days. | 2/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | Each elevator in the building shall be assigned a uniquie aphabetical or numerical identification painted on, engraved, or securely attached to the car operating panel. Note: This plate shall should read car 4 instead of car 1. | 2/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency lighting shall work. | 10/10/2025 |