Inspection
Inspection Details
Equipment ID
6073
6073
Inspection Date
10/13/2025
10/13/2025
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Michael Amador
Michael Amador
Mechanic Name
Steven Hatcher
Steven Hatcher
Relief Valve Pressure
na
na
Slide
32
32
Governor Rope Pull
250/700
250/700
Door Closing Force
22
22
External ID
79ca520e-9012-4bcd-8255-7021dfe93d25
79ca520e-9012-4bcd-8255-7021dfe93d25
Location
Arch Hotel Project Owner LLC
315 Chestnut St, St. Louis, MO
Phone: (314) 655-1234
315 Chestnut St, St. Louis, MO
Phone: (314) 655-1234
Owner
Attn: Don Macbush
Hyatt Regency St Louis at the Arch
N 4th St at Chestnut St, St. Louis, MO 63102
Phone: (314) 342-4637
Email: accountingstlrs@hyatt.com
Hyatt Regency St Louis at the Arch
N 4th St at Chestnut St, St. Louis, MO 63102
Phone: (314) 342-4637
Email: accountingstlrs@hyatt.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | Yes | No | Counterweight buffer is being compressed 1" when car is at top landing. Shorten suspension ropes to maintian proper counterweight runby. | 3/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.18 - Traction drive machines | 8.11.2.1.2(p) | Yes | No | Traction machine leaking oil onto outboard side of drive sheave. Repair leaking seal. | 3/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | Yes | Emergency brake is not working due to oil leaking onto braking surface and brake pads. Elevator removed from service until repaired. | 3/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | Yes | No | Counterweight buffer is being compressed 1" when car is at top landing. Shorten suspension ropes to maintain proper counterweight runby. | 2/23/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.18 - Traction drive machines | 8.11.2.1.2(p) | Yes | No | Traction machine leaking oil onto outboard side of drive sheave. Repair leaking seal. | 2/23/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pits | 10/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing hoistway door gibs on basement doors | 10/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Repair lighting above stairway accessing machine room to provide safe access for workers | 10/15/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work. Repair same | 10/15/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Fire seal hoistway (corner) near floor 1. | 12/9/2025 |
| A17.1-2016 : Elevators | 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators | 2.27.1 | Yes | No | FEO Phase I and II need to be tested when hall risers are installed. | 12/9/2025 |