Inspection
Inspection Details
Equipment ID
12355
12355
Inspection Date
10/6/2025
10/6/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Dequarius Millett
Dequarius Millett
Mechanic Name
Relief Valve Pressure
N/A
N/A
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
5bbe398d-be6c-411f-8a58-ae187c432cd9
5bbe398d-be6c-411f-8a58-ae187c432cd9
Location
Mary Grove Childrens Home
2705 Mullanphy Ln, Florissant, MO
Phone: (314) 837-1702
2705 Mullanphy Ln, Florissant, MO
Phone: (314) 837-1702
Owner
Attn: Mary Grove Children's Home
Mary Grove Children's Home
2705 Mullanphy Ln, Florissant, MO 63031
Phone: (314) 837-1702
Email: tgregory@mgstl.org
Mary Grove Children's Home
2705 Mullanphy Ln, Florissant, MO 63031
Phone: (314) 837-1702
Email: tgregory@mgstl.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 10/3/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work on emergency power (pull 110v) | 1/23/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 2.14.2.3 | No | No | Car fan, on car top has no cover. Provide. | 10/16/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | Machine room ventilation unit not working, make so. | 10/16/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | Yes | No | Sump pump in the pit is not plugged in. Determine if unit works, if not replace.if electrical issue then repair outlet. | 1/23/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Provide machine room door to be self closing. | 10/16/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 10/16/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work on emergency power | 10/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car fan, on car top has no cover. Fan must have cover | 10/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Machine room ventilation unit not working | 10/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Sump pump in the pit is not plugged in. Determine if unit works, if not replace. If electrical issue then repair outlet | 10/16/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Provide machine room door to be self closing and self locking | 10/16/2025 |