Inspection
Inspection Details
Equipment ID
6903
6903
Inspection Date
11/21/2017
11/21/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
Location
AT & T- Olive Street
2651 Olive St, St. Louis, MO
Phone: (314) 658-5381
2651 Olive St, St. Louis, MO
Phone: (314) 658-5381
Owner
AT & T- Olive Street
2651 Olive St, Room 135, St. Louis, MO 63103
2651 Olive St, Room 135, St. Louis, MO 63103
Billing
Attn: AT & T Elevator Management c/o Lerch Bates
4201 Northview Drive Suite 314, , MD 20716
4201 Northview Drive Suite 314, , MD 20716
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - red tag | Yes | Yes | Car is red-tagged. Governor rope pulling through jaws and will not set safeties. Annual test was completed. | 3/20/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Replace missing car station call lights. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 11/19/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair loose door astrigal. | 9/22/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Governor rope pulling through jaws and will not set safeties. Red Tag Issued | 9/22/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Category 5 weight testing has not been performed since 2016. Category 5 testing shall be performed and witnessed immediately. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting is not working. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Replace missing/broken car station call buttons. | 9/22/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self-closing and self-locking. Mechanic stated the lock jams from the inside. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Machinery, controllers, governors, disconnects shall be numbered conspicuously. Governors are not numbered. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Cartop light does not work. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Suspension means shall have proper data tags. | 12/18/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept dry. Remove rust from pit equipment, repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak. | 12/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Governor rope shall be shortened/replaced to allow proper tension device clearance. | 12/18/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting is not working. | 12/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Multi-year violation. | 12/18/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. (2nd Notice) | 12/18/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service shall be tested and documented monthly. | 12/18/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | Safeties failed to fully set and stop elevator. Unit continue to run downward after set. (SOS worked, Gov worked) 8.6.4.19.2(b) REDTAG ISSUED, Unit has been taken out of service. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. Violation: no required documents onsite. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | No Fire Service Testing Logs, tested monthly | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Suspension means shall have proper data tags. |