Inspection
Inspection Details
Equipment ID
8659
8659
Inspection Date
10/22/2025
10/22/2025
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Amador
Michael Amador
Mechanic Name
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
768313e0-9925-4cf8-b2de-0993f7cb035a
768313e0-9925-4cf8-b2de-0993f7cb035a
Location
Leonardo Bldg
4166 Lindell Blvd, St. Louis, MO
Phone: (888) 213-7363
4166 Lindell Blvd, St. Louis, MO
Phone: (888) 213-7363
Owner
Attn: Revival STL Construction, LLC
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The cab lighting shall be properly guarded. | 12/15/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Replace the worn counterweight rollers. | 12/15/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. | 12/15/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Replace the worn pick-up rollers at the 5th & 6th floor. | 12/15/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The car door restrictor shall be operational. | 11/25/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Install an anti-spin device on the hoist ropes. | 11/25/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes are rouged and have reached minimum diameter in several areas. Replacement of the hoist ropes is required. | 11/25/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 12/2/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate in machine room. | 12/1/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | All smoke detectors need to be tested | 10/15/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room shall be self closing and self locking | 10/15/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)3 | Yes | No | Grating in machine deck floor shall be fastened down or covered and fastened | 10/15/2021 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | Fire extinguisher in machine room needs replacing or servicing | 10/15/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car shall work with failure indication and have battery backup for modem on phone line | 10/15/2021 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.7.1.8 | Yes | No | Install code data plate containing all altered equipment code references to be installed on controller | 10/15/2021 |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.10.2.2.5(b) | Yes | No | Runby signage shall be posted in pit | 10/15/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) | No | No | Smoke detector in the elevator machine room shall flash the in car fire hat | 10/20/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept dry and clear of debris | 9/29/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 2/14/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete due to water in pit, safeties must be set. Re-inspection required | 2/14/2023 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | No | No | Provide feeder location on the main line disconnect, in the elevator machine room.NEC620 | 9/29/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | No | No | Provide feeder location on the 110v. disconnect in the elevator machine room.NEC620 | 9/29/2025 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.1 | No | No | Provide code compliant means to access secondary level in the elevator machine room. | 9/29/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work. | 10/4/2024 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide current year tested fire extinguisher in the elevator machine room. | 9/29/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | Yes | No | Sump pump in the pit is not working, repair/replace as needed. | 10/4/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Remove water from the pit. | 9/29/2025 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.1 | No | No | Door knob to access the machine room is damaged, replace. | 9/29/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperative emergency phone | 9/29/2025 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | No | No | Cab lighting shall be protected | 9/29/2025 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | No | No | Two lamps are required. Lamps shall operate independently of each other. | 9/29/2025 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | No | No | Cab lighting shall be wiring shall meet the NEC | 10/23/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove standing water from the elevator pit. | 10/23/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean and dry. Sump not working. | 10/23/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | No | No | Provide feeder location on the main line disconnect, in the elevator machine room.NEC620 | 10/23/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | No | No | Provide feeder location on the 110v. disconnect in the elevator machine room.NEC620 | 10/23/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Emergency light fixture lens is broken | 10/23/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Hoist ropes and sheave are covered in grease. Ropes need cleaned | 10/23/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Car lights need wired properly | 10/23/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone does not dial. No phone line | 10/23/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher shall be kept up to date. | 10/23/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher shall be kept up to date | 10/23/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Car lights needs wired properly per NEC | 10/23/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | No | No | Provide feeder location on the 110v. disconnect in the elevator machine room.NEC620 | 10/23/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone and light shall be operational. | |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.14.5.7 | Yes | No | Car Door restrictor shall prevent doors from opening more than 4" | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.3 | No | No | Sump pump is not operational with approx 10" of water. Pit shall be kept clean/dry and Permanent provisions shall be made to prevent accumulation of groundwater in the pit |