Inspection
Inspection Details
Equipment ID
13736
13736
Inspection Date
10/22/2025
10/22/2025
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Amador
Michael Amador
Mechanic Name
Richard Babor III
Richard Babor III
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
35 / 171
35 / 171
Door Closing Force
Manual
Manual
External ID
f7908c29-7af9-45ef-964e-874dcdb68114
f7908c29-7af9-45ef-964e-874dcdb68114
Location
The Ellsworth
4405 W Pine Blvd, St. Louis, MO
Phone: (314) 535-6466
4405 W Pine Blvd, St. Louis, MO
Phone: (314) 535-6466
Owner
Attn: Revival STL Construction, LLC
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@luxliving.co
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@luxliving.co
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | The elevator pit shall be kept dry. | 6/3/2019 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Newly installed plumbing vent is vented into machine room. Either remove pipe or move machine fence to get pipe out of machine room. | 11/18/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | Provide written maintenance control program on site for each elevator. | 11/18/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher in the machine room is outdated. Update fire extinguisher | 12/15/2021 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit shall be clean of debris. | 12/15/2021 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | x | White PVC vent pipe shall be removed from machine room, it is in front of the main line disconnect, this is the second time this has been written up. | 9/1/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Emergency light shall be made operational | 9/1/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | Provide maintenance control programs on site for each elevator | 9/8/2023 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pits shall be kept clean of debris | 9/8/2023 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit shall be kept clean of water and debris | 9/8/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Car top needs cleaned | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Machine is covered in oil and needs cleaned | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit needs cleaned | |||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Two of the hoist ropes are crossed and one shackle has a hoist rope incorrectly seated. | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Runby is 2 - Hoist ropes need shortened. | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | Car lighting is hanging and needs properly fastened | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Repair Broken Flex to electrical box on crosshead | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Remove unused hanging and broken electrical cable from hoistway (can be seen from pit) | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Manual Gate is missing a handle and creates a pinch hazard |