Inspection
Inspection Details
Equipment ID
22279
22279
Inspection Date
9/26/2025
9/26/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Michael Beachner
Michael Beachner
Relief Valve Pressure
590
590
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
25
25
External ID
43fc2059-2b84-4b8d-87d1-2dc019d4c15c
43fc2059-2b84-4b8d-87d1-2dc019d4c15c
Location
Residences @ New Longview Apt
3331 SW Kessler Dr, Lee's Summit, MO
Phone: (000) 000-0000
3331 SW Kessler Dr, Lee's Summit, MO
Phone: (000) 000-0000
Owner
Attn: Amanda Middaugh
JVM Realty
3301 SW Kessler Dr, Lee's Summit, MO 64081
Phone: (816) 767-9999
Email: amiddaugh@jvmrealty.com
JVM Realty
3301 SW Kessler Dr, Lee's Summit, MO 64081
Phone: (816) 767-9999
Email: amiddaugh@jvmrealty.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Perform monthly fire service test and post log in the machine room. | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | monthly fire service test log in the machine room is not being filled out monthly | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | post copy of the state operating certificate in the machine room | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | replace burnt out cab ceiling light bulb, required to have at least two working light bulbs | 1/1/2021 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the machine room is from 2017, a new copy is to be displayed every year | 12/1/2022 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.11.3.1.1(e) | No | No | only one of the car ceiling light bulbs is working, replace burnt out bulb, required to have two working bulbs | 12/1/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the elevator machine room expired in 2017, update with a copy of the current certificate annually | 6/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | replace burnt out cab ceiling light bulbs, required to have at least two working light bulbs | 6/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Elevator certificate in the machine room expired in 2022, update with a new certificate annually | 6/25/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | Replace burnt out cab ceiling light bulb, required to have two working light bulbs | 6/25/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone, couldn’t hear what operator was saying, the phone kept cutting out. | 6/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Elevator certificate in the machine room expired in 2022, update with a new certificate annually | 12/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | Replace burnt out cab ceiling light bulb, required to have two working light bulbs | 12/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | Machine room air conditioning unit is not working, it’s flashing an error. Do not find a remote to operate the air conditioning unit in the machine room. | 10/28/2025 |