Inspection
Inspection Details
Equipment ID
22278
22278
Inspection Date
9/26/2025
9/26/2025
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Michael Beachner
Michael Beachner
Relief Valve Pressure
540
540
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
22
22
External ID
e80be6a0-bc71-434a-bd94-f5d222567a1b
e80be6a0-bc71-434a-bd94-f5d222567a1b
Location
Residences @ New Longview Apt
3311 SW Kessler Dr, Lee's Summit, MO
Phone: (000) 000-0000
3311 SW Kessler Dr, Lee's Summit, MO
Phone: (000) 000-0000
Owner
Attn: Amanda Middaugh
JVM Realty
3301 SW Kessler Dr, Lee's Summit, MO 64081
Phone: (816) 767-9999
Email: amiddaugh@jvmrealty.com
JVM Realty
3301 SW Kessler Dr, Lee's Summit, MO 64081
Phone: (816) 767-9999
Email: amiddaugh@jvmrealty.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | repair door restrictor | 8/17/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Repair door restrictor, it is missing parts | 11/15/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | maintain dry pit, standing water in the pit at the time of the inspection | 4/30/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Perform monthly fire service test and post log in the machine room. | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.1 - Top-of-car stop switch | 8.11.2.1.3(a) | No | No | the car top stop switch on the control station is missing, the stop switch on the pendant station works | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | clean the pit, oil and water mixture, pistons are starting to rust | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | the door restrictor is missing parts so that it will not work | 10/12/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | replace burnt out cab light bulb, only has one working light bulb | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | the monthly fie service test log in the machine room needs to be filled out monthly | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | post copy of the state operating certificate in the machine room | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | replace burnt out cab ceiling light, required to have at least two working light bulbs | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | repair the door restrictor, the hook is on the car top | 11/9/2021 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the machine room is from 2017, a new copy is to be displayed every year | 6/13/2023 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.11.3.1.1(e) | No | No | only one of the cab ceiling lights is working, required to have two working light bulbs | 6/13/2023 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.3.1.5(a) | No | No | sump pump is plugged into the GFCI outlet, it is to be plugged into the non GFCI outlet | 6/13/2023 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | water, oil, black mold mixture on the pit floor needs to be cleaned up | 6/13/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the elevator machine room expired in 2018, update with a copy of the current certificate annually | 6/2/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | replace burnt out light bulb in cab ceiling light fixture, required to have at least two working light bulbs | 6/2/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | clean the pit, looks like there is mold growing on the pit floor | 6/2/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 2.14.7 | No | No | Replace car top light fixture, the fixture is broken in a way that it will not take a light bulb (2.14.7.1.4) | 7/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate in the machine room expired in 2022, update with a new copy of the certificate annually | 7/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit | 7/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.12 - Car enclosure | 2.14 | No | No | Replace missing/broken trim ring on the car operating panel (2.14.1.2.4) | 7/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate in the machine room expired in 2022, update with a new copy of the certificate annually | 12/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | No | No | Heat detector in the pit is not to hang by the wires, mount detector to the wall box | 12/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | No | No | Heat detector in the pit is not to hang by the wires, mount detector to the wall box | 10/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | No | No | Pit has standing water and oil mixture on pit floor, clean pit, maintain dry pit (2.2.2.3) | 10/28/2025 |