A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Post current operating certificate.
|
12/3/2018
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
No
|
No
|
A new drop ceiling has been installed at some point with the anchor bolts protruding through the car top approximately 4”. The anchor bolts shall be cut off smooth on the cart top as not to cause a tripping hazard or potential injury to maintenance and emergency personnel.
|
10/29/2025
|
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
No
|
No
|
This unit has an OSV that is due for testing in 2024. This testing shall be performed before the end of the year
|
10/29/2025
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A copy of the current operating certificate shall be displayed in the machine room
|
10/29/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
No
|
No
|
This unit has had a drop ceiling installed and the bolts are sticking through the car top, the bolts need to be cut off so that they don't cause a tripping hazard for the maintenance personnel working on the cartop
|
10/29/2025
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
No
|
No
|
Pit needs to be cleaned
|
10/29/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
No
|
No
|
Fire extinguisher in machine room is expired. Replace or have serviced
|
10/29/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
No
|
No
|
Cartop needs to be cleaned
|
10/29/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
Yes
|
No
|
A new drop ceiling has been installed at some point with the anchor bolts protruding through the car top approximately 4". The anchor bolts shall be cut off smooth on the car top as not to cause a tripping hazard or potential injury to maintenance or emergency personnel. This is the second notice about the anchor bolts, needs to be completed within 30 days. Re-inspection required
|
10/29/2025
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A copy of the current state certificate shall be displayed in the machine room
|
10/29/2025
|