Inspection
Inspection Details
Equipment ID
1915
1915
Inspection Date
1/9/2019
1/9/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Alex Brinkman
Alex Brinkman
Relief Valve Pressure
Slide
8.5
8.5
Governor Rope Pull
80/480
80/480
Door Closing Force
27
27
External ID
0f67beaf-b284-4556-9a4c-a90756d83ff2
0f67beaf-b284-4556-9a4c-a90756d83ff2
Location
Hilton at the Ballpark
1 S BROADWAY, SAINT LOUIS, MO
1 S BROADWAY, SAINT LOUIS, MO
Owner
Lodging Hospitality Management
111 WEST PORT PLZ STE 500, SAINT LOUIS, MO 63146-3015
111 WEST PORT PLZ STE 500, SAINT LOUIS, MO 63146-3015
Billing
Attn: Hilton at the Ballpark
1 S BROADWAY, SAINT LOUIS, MO 63102-1703
1 S BROADWAY, SAINT LOUIS, MO 63102-1703
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - n/a | n/a | No | No | Pit needs to be cleaned. | 8/12/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 | Yes | No | Cables need to be shortened. | 4/1/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 2/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 8.6.4.2 | No | No | Governor cables were found to be undersized. They may need to be replaced in the future. Recommendation only. | 11/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone inoperative. | 12/3/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 3/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 1/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | 2.7.1 The elevator machine room has been damaged by the malfunctioning HVAC system resulting in drywall damage and the presence of mold. The machine room shall be repaired to meet the integrity of the room. | 1/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.8 - Top emergency exit | 2.14.1.5 | No | No | The car top escape hatch switch has been disabled. Re-enable the escape hatch switch to operate. | 1/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | 2.27.3.1.1 The fireman’s service phase I key switch is deteriorating and shall be replaced. Reinspection required. | 4/23/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | 1/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller | 1/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | No | No | The elevator machine room has been damaged by the malfunctioning HVAC system, resulting in drywall damage and the presence of mold. The machine room shall be repaired to meet the integrity of the room. HVAC unit in machine room still leaks at condensate pump, needing repair. | 1/13/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes are at a minimum diameter, need to replace within 90 days. Re-inspection required | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop needs to be cleaned | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Access to the machine room shall be clear and unobstructed. Remove all items from the stairway leading to the machine room |